Voltage Irregularity Report
Brieske residence, Orcutt CA · All recorded history · generated 2026-09-23 10:16:11 PDT
Since PG&E's monitor went up24 hours3 days7 days14 days30 daysAll time
☰ Simple one-page versionDownload .txtDownload .csvPrint / save PDF
Measurement method: three TP-Link EP25 metering outlets record true-RMS line voltage once per second on both 120 V legs of the split-phase service. A Tesla Wall Connector supplies the 240 V line-to-line reference and grid frequency, which is independent of the neutral. A Ting (Whisker) sensor on Leg A samples far faster than 1 Hz and retains the lowest and highest voltage it sees, so it resolves brief excursions that a 1 s RMS average necessarily flattens in both directions. Where the two disagree, the Ting figure is the closer estimate of the real extreme.
What is listed: any reading below 114 V (the ANSI C84.1 Range A lower limit) and any reading above 127 V (the Range B upper limit) at 120 V nominal. Undervoltage dims and stalls equipment; sustained overvoltage damages it, so both are reported.
36,244 samples logged today across 87 retained detail files.
Also recorded but not listed individually: 209 brief high readings on a 120 V branch meter, peaking at 130.1 V. These are held back for two reasons: readings between 126 V and 127 V are inside ANSI Range B, which the standard tolerates as occasional; and none of them were confirmed by the neutral-independent 240 V line-to-line reference, which never left its limits. They are reported as a count so that nothing is hidden, not because they are being claimed.
Lowest branch meter
101.20 V
Lowest Ting reading
84.84 V
Lowest 240 V reference
220.3 V
Time out of range
15 min 49 s
When they happen
00:00 ×3 01:00 ×1 02:00 ×1 03:00 ×1 04:00 ×1 05:00 ×4 07:00 ×2 08:00 ×12 09:00 ×3 10:00 ×5 11:00 ×4 15:00 ×3 16:00 ×6 17:00 ×9 18:00 ×7 19:00 ×11 20:00 ×4 21:00 ×7 22:00 ×7 23:00 ×4
Irregularities (newest first)
1. 2026-09-23 00:00:22 UNDERVOLTAGE
lasted 3 seconds · 4 samples out of range · outside Range A
MINOR LEG IMBALANCE| Lowest reading | 113.75 V on 3D Printer - Mikes Room |
|---|
| Leg A / Leg B | 120.55 V / 116.73 V (3.82 V split) |
|---|
| 240 V service reference | 235.9 V |
|---|
| Meters affected | 3D Printer - Mikes Room |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 113.8 V, below the 114 V Range A limit
The legs differed by more than the tracking threshold, but neither fell far enough below its calm baseline or below the ANSI Range A limit to count as a sag. Normal load imbalance looks like this.
2. 2026-09-01 21:15:16 UNDERVOLTAGE
lasted 2 minutes 45 seconds · 166 samples out of range · outside Range A
LOCAL/BRANCH DROP| Lowest reading | 113.19 V on 3D Printer - Mikes Room |
|---|
| Leg A / Leg B | 120.36 V / 113.45 V (6.91 V split) |
|---|
| 240 V service reference | 233.1 V |
|---|
| Meters affected | 3D Printer - Mikes Room, Computer and TV - Mikes Room |
|---|
Ting recorded 118.50 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.2 V, below the 114 V Range A limit
A branch measurement fell without confirming movement at the 240 V service reference.
3. 2026-09-01 21:14:49 UNDERVOLTAGE
lasted 7 seconds · 8 samples out of range · outside Range A
LOCAL/BRANCH DROP| Lowest reading | 113.96 V on 3D Printer - Mikes Room |
|---|
| Leg A / Leg B | 120.36 V / 113.45 V (6.91 V split) |
|---|
| 240 V service reference | 233.1 V |
|---|
| Meters affected | 3D Printer - Mikes Room |
|---|
Ting recorded 118.50 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
A branch measurement fell without confirming movement at the 240 V service reference.
4. 2026-08-23 16:31:26 UNDERVOLTAGE
lasted 17 seconds · 18 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 101.20 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 101.20 V / 123.09 V (21.89 V split) |
|---|
| 240 V service reference | 221.8 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 84.84 V during this event
retained 2026-08-23 16:31:25 = 84.84 V (exact timestamp)
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 101.2 V, below the 110 V Range B limit
- independent Ting sensor 84.8 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
5. 2026-08-23 15:24:40 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 105.95 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 105.95 V / 121.41 V (15.46 V split) |
|---|
| 240 V service reference | 231.1 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 105.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 106.0 V, below the 110 V Range B limit
- independent Ting sensor 105.2 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
6. 2026-08-23 15:04:33 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 106.35 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 106.35 V / 121.52 V (15.17 V split) |
|---|
| 240 V service reference | 228.8 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 106.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 106.3 V, below the 110 V Range B limit
- independent Ting sensor 106.1 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
7. 2026-08-23 07:34:13 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 108.05 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 108.05 V / 122.30 V (14.25 V split) |
|---|
| 240 V service reference | 226.9 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 107.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 108.0 V, below the 110 V Range B limit
- independent Ting sensor 107.2 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
8. 2026-08-23 02:20:21 UNDERVOLTAGE
lasted 11 seconds · 12 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 106.65 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 106.65 V / 122.51 V (15.86 V split) |
|---|
| 240 V service reference | 225.5 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 106.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 106.7 V, below the 110 V Range B limit
- independent Ting sensor 106.1 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
9. 2026-08-23 01:52:44 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LOCAL/BRANCH DROP| Lowest reading | 107.02 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 107.02 V / 121.28 V (14.27 V split) |
|---|
| 240 V service reference | 231.9 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 119.70 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 107.0 V, below the 110 V Range B limit
A branch measurement fell without confirming movement at the 240 V service reference.
10. 2026-08-22 23:02:00 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 108.56 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 108.56 V / 119.57 V (11.01 V split) |
|---|
| 240 V service reference | 231.1 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 115.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 108.6 V, below the 110 V Range B limit
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
11. 2026-08-22 23:01:30 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range A
LEG A SUPPLY SAG| Lowest reading | 112.00 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 108.56 V / 119.57 V (11.01 V split) |
|---|
| 240 V service reference | 231.1 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 115.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 112.0 V, below the 114 V Range A limit
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
12. 2026-08-22 22:28:30 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range A
LEG A SUPPLY SAG| Lowest reading | 112.51 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 112.51 V / 119.12 V (6.61 V split) |
|---|
| 240 V service reference | 229.3 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 106.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 112.5 V, below the 114 V Range A limit
- independent Ting sensor 106.1 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
13. 2026-08-22 21:41:20 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 107.71 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 107.71 V / 117.18 V (9.47 V split) |
|---|
| 240 V service reference | 228.2 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 105.70 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 107.7 V, below the 110 V Range B limit
- independent Ting sensor 105.7 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
14. 2026-08-21 19:51:42 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 105.98 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 105.98 V / 122.14 V (16.16 V split) |
|---|
| 240 V service reference | 226.8 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 106.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 106.0 V, below the 110 V Range B limit
- independent Ting sensor 106.2 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
15. 2026-08-21 19:50:57 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range A
LEG A SUPPLY SAG| Lowest reading | 113.98 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 105.98 V / 122.14 V (16.16 V split) |
|---|
| 240 V service reference | 226.8 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 106.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
- independent Ting sensor 106.2 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
16. 2026-08-21 17:19:49 UNDERVOLTAGE
lasted 11 seconds · 12 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 104.89 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 104.89 V / 122.97 V (18.08 V split) |
|---|
| 240 V service reference | 226.0 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 103.50 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 104.9 V, below the 110 V Range B limit
- independent Ting sensor 103.5 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
17. 2026-08-21 16:51:39 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 107.63 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 107.63 V / 121.16 V (13.53 V split) |
|---|
| 240 V service reference | 226.4 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 106.80 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 107.6 V, below the 110 V Range B limit
- independent Ting sensor 106.8 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
18. 2026-08-21 16:29:02 UNDERVOLTAGE
lasted 18 seconds · 18 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 104.01 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 104.01 V / 118.75 V (14.73 V split) |
|---|
| 240 V service reference | 222.5 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 86.35 V during this event
retained 2026-08-21 16:28:50 = 86.35 V (exact timestamp)
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 104.0 V, below the 110 V Range B limit
- independent Ting sensor 86.3 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
19. 2026-08-21 16:28:51 UNDERVOLTAGE
lasted 5 seconds · 6 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 104.52 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 104.01 V / 118.75 V (14.73 V split) |
|---|
| 240 V service reference | 222.5 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 86.35 V during this event
retained 2026-08-21 16:28:50 = 86.35 V (exact timestamp)
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 104.5 V, below the 110 V Range B limit
- independent Ting sensor 86.3 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
20. 2026-08-21 10:14:44 UNDERVOLTAGE
lasted 5 seconds · 6 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 104.49 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 104.49 V / 123.26 V (18.77 V split) |
|---|
| 240 V service reference | 225.9 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 97.71 V during this event
retained 2026-08-21 10:14:47 = 97.71 V (exact timestamp)
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 104.5 V, below the 110 V Range B limit
- independent Ting sensor 97.7 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
21. 2026-08-17 11:32:41 UNDERVOLTAGE
lasted 38 seconds · 38 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 104.95 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 104.95 V / 123.10 V (18.15 V split) |
|---|
| 240 V service reference | 224.5 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 101.70 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 105.0 V, below the 110 V Range B limit
- independent Ting sensor 101.7 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
22. 2026-08-17 11:32:11 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 105.77 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 104.95 V / 123.10 V (18.15 V split) |
|---|
| 240 V service reference | 224.5 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 101.70 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 105.8 V, below the 110 V Range B limit
- independent Ting sensor 101.7 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
23. 2026-08-17 10:09:13 UNDERVOLTAGE
lasted 1 second · 2 samples out of range · outside Range B
LEG A MULTI-METER SAG| Lowest reading | 106.66 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 106.66 V / 123.16 V (16.50 V split) |
|---|
| 240 V service reference | 239.4 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 107.30 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 106.7 V, below the 110 V Range B limit
- independent Ting sensor 107.3 V
The Leg A branch meter and independent Ting sensor fell while Leg B stayed comparatively stable; the 240 V reference did not show a matching drop.
24. 2026-08-17 09:29:01 UNDERVOLTAGE
lasted 5 seconds · 6 samples out of range · outside Range B
LOCAL/BRANCH DROP| Lowest reading | 108.87 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 108.87 V / 122.10 V (13.23 V split) |
|---|
| 240 V service reference | 235.4 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 120.70 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 108.9 V, below the 110 V Range B limit
A branch measurement fell without confirming movement at the 240 V service reference.
25. 2026-08-16 21:43:31 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 106.30 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 106.30 V / 122.39 V (16.09 V split) |
|---|
| 240 V service reference | 227.0 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 105.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 106.3 V, below the 110 V Range B limit
- independent Ting sensor 105.2 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
26. 2026-08-16 19:36:10 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range A
LOCAL/BRANCH DROP| Lowest reading | 113.86 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 113.86 V / 120.41 V (6.55 V split) |
|---|
| 240 V service reference | 237.8 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 120.90 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
A branch measurement fell without confirming movement at the 240 V service reference.
27. 2026-08-16 17:02:51 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 106.91 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 106.91 V / 120.75 V (13.84 V split) |
|---|
| 240 V service reference | 226.9 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 106.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 106.9 V, below the 110 V Range B limit
- independent Ting sensor 106.4 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
28. 2026-08-16 16:58:01 UNDERVOLTAGE
lasted 16 seconds · 17 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 106.47 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 106.47 V / 121.62 V (15.15 V split) |
|---|
| 240 V service reference | 225.8 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 104.90 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 106.5 V, below the 110 V Range B limit
- independent Ting sensor 104.9 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
29. 2026-08-16 16:08:16 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 108.56 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 108.56 V / 123.13 V (14.57 V split) |
|---|
| 240 V service reference | 233.3 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 106.80 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 108.6 V, below the 110 V Range B limit
- independent Ting sensor 106.8 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
30. 2026-08-16 15:17:49 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LEG A MULTI-METER SAG| Lowest reading | 108.60 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 108.60 V / 122.20 V (13.60 V split) |
|---|
| 240 V service reference | 237.7 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 106.00 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 108.6 V, below the 110 V Range B limit
- independent Ting sensor 106.0 V
The Leg A branch meter and independent Ting sensor fell while Leg B stayed comparatively stable; the 240 V reference did not show a matching drop.
31. 2026-08-16 10:51:48 UNDERVOLTAGE
lasted 8 seconds · 9 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 105.47 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 105.47 V / 124.47 V (19.00 V split) |
|---|
| 240 V service reference | 225.5 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 101.90 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 105.5 V, below the 110 V Range B limit
- independent Ting sensor 101.9 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
32. 2026-08-15 18:02:41 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 102.55 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 102.55 V / 122.64 V (20.09 V split) |
|---|
| 240 V service reference | 226.5 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 102.30 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 102.5 V, below the 110 V Range B limit
- independent Ting sensor 102.3 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
33. 2026-08-15 11:03:05 UNDERVOLTAGE
lasted 1 second · 2 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 106.62 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 106.62 V / 123.47 V (16.85 V split) |
|---|
| 240 V service reference | 226.9 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 106.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 106.6 V, below the 110 V Range B limit
- independent Ting sensor 106.4 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
34. 2026-08-15 11:01:41 UNDERVOLTAGE
lasted 5 seconds · 6 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 108.36 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 106.62 V / 123.47 V (16.85 V split) |
|---|
| 240 V service reference | 226.9 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 106.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 108.4 V, below the 110 V Range B limit
- independent Ting sensor 106.4 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
35. 2026-08-14 18:14:15 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LEG A MULTI-METER SAG| Lowest reading | 106.26 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 106.26 V / 121.22 V (14.96 V split) |
|---|
| 240 V service reference | 235.5 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 106.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 106.3 V, below the 110 V Range B limit
- independent Ting sensor 106.4 V
The Leg A branch meter and independent Ting sensor fell while Leg B stayed comparatively stable; the 240 V reference did not show a matching drop.
36. 2026-08-14 18:01:24 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 106.41 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 106.41 V / 121.96 V (15.55 V split) |
|---|
| 240 V service reference | 224.0 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 104.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 106.4 V, below the 110 V Range B limit
- independent Ting sensor 104.1 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
37. 2026-08-14 17:23:47 UNDERVOLTAGE
lasted 35 seconds · 36 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 104.33 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 104.33 V / 122.37 V (18.04 V split) |
|---|
| 240 V service reference | 225.5 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 103.50 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 104.3 V, below the 110 V Range B limit
- independent Ting sensor 103.5 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
38. 2026-08-14 17:22:50 UNDERVOLTAGE
lasted 23 seconds · 24 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 106.69 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 104.33 V / 122.37 V (18.04 V split) |
|---|
| 240 V service reference | 225.5 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 103.50 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 106.7 V, below the 110 V Range B limit
- independent Ting sensor 103.5 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
39. 2026-08-13 00:00:27 UNDERVOLTAGE
lasted 3 seconds · 4 samples out of range · outside Range A
MINOR LEG IMBALANCE| Lowest reading | 113.04 V on 3D Printer - Mikes Room |
|---|
| Leg A / Leg B | 119.94 V / 115.94 V (4.00 V split) |
|---|
| 240 V service reference | 234.6 V |
|---|
| Meters affected | 3D Printer - Mikes Room |
|---|
Ting recorded 118.90 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.0 V, below the 114 V Range A limit
The legs differed by more than the tracking threshold, but neither fell far enough below its calm baseline or below the ANSI Range A limit to count as a sag. Normal load imbalance looks like this.
40. 2026-08-02 18:08:25 UNDERVOLTAGE
lasted 29 seconds · 30 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 105.54 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 105.54 V / 122.12 V (16.58 V split) |
|---|
| 240 V service reference | 224.8 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 104.00 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 105.5 V, below the 110 V Range B limit
- independent Ting sensor 104.0 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
41. 2026-08-02 17:46:30 UNDERVOLTAGE
lasted 4 seconds · 4 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 107.35 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 107.35 V / 120.26 V (12.91 V split) |
|---|
| 240 V service reference | 225.7 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 106.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 107.3 V, below the 110 V Range B limit
- independent Ting sensor 106.4 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
42. 2026-08-02 17:24:38 UNDERVOLTAGE
lasted 3 seconds · 4 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 106.07 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 106.07 V / 122.58 V (16.52 V split) |
|---|
| 240 V service reference | 227.1 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 104.80 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 106.1 V, below the 110 V Range B limit
- independent Ting sensor 104.8 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
43. 2026-08-02 09:34:27 UNDERVOLTAGE
lasted 4 seconds · 5 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 105.09 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 105.09 V / 122.60 V (17.51 V split) |
|---|
| 240 V service reference | 232.1 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 103.50 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 105.1 V, below the 110 V Range B limit
- independent Ting sensor 103.5 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
44. 2026-08-02 08:52:17 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range A
LOCAL/BRANCH DROP| Lowest reading | 111.42 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 111.42 V / 122.09 V (10.67 V split) |
|---|
| 240 V service reference | 236.9 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 121.90 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 111.4 V, below the 114 V Range A limit
A branch measurement fell without confirming movement at the 240 V service reference.
45. 2026-08-02 08:14:16 UNDERVOLTAGE
lasted 0 seconds · 1 sample out of range · outside Range B
LOCAL/BRANCH DROP| Lowest reading | 106.84 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 106.84 V / 121.11 V (14.27 V split) |
|---|
| 240 V service reference | 235.2 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 121.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 106.8 V, below the 110 V Range B limit
A branch measurement fell without confirming movement at the 240 V service reference.
46. 2026-07-29 19:26:28 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range A
LOCAL/BRANCH DROP| Lowest reading | 112.91 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 112.91 V / 119.31 V (6.41 V split) |
|---|
| 240 V service reference | 232.0 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 118.70 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 112.9 V, below the 114 V Range A limit
A branch measurement fell without confirming movement at the 240 V service reference.
47. 2026-07-25 07:15:33 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range A
LOCAL/BRANCH DROP| Lowest reading | 113.03 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 113.03 V / 121.53 V (8.50 V split) |
|---|
| 240 V service reference | 236.6 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 120.90 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.0 V, below the 114 V Range A limit
A branch measurement fell without confirming movement at the 240 V service reference.
48. 2026-07-24 19:44:06 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range A
LOCAL/BRANCH DROP| Lowest reading | 111.52 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 111.52 V / 119.60 V (8.08 V split) |
|---|
| 240 V service reference | 234.8 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 119.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 111.5 V, below the 114 V Range A limit
A branch measurement fell without confirming movement at the 240 V service reference.
49. 2026-07-24 19:10:12 UNDERVOLTAGE
lasted 1 second · 2 samples out of range · outside Range B
LOCAL/BRANCH DROP| Lowest reading | 105.42 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 105.42 V / 120.44 V (15.02 V split) |
|---|
| 240 V service reference | 233.7 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 120.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 105.4 V, below the 110 V Range B limit
A branch measurement fell without confirming movement at the 240 V service reference.
50. 2026-07-24 18:28:43 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LOCAL/BRANCH DROP| Lowest reading | 109.48 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 109.48 V / 120.06 V (10.58 V split) |
|---|
| 240 V service reference | 232.4 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 118.80 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 109.5 V, below the 110 V Range B limit
A branch measurement fell without confirming movement at the 240 V service reference.
51. 2026-07-24 18:09:04 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 105.25 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 105.25 V / 121.06 V (15.81 V split) |
|---|
| 240 V service reference | 228.3 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 103.30 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 105.2 V, below the 110 V Range B limit
- independent Ting sensor 103.3 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
52. 2026-07-24 17:53:36 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LOCAL/BRANCH DROP| Lowest reading | 103.78 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 103.78 V / 121.70 V (17.92 V split) |
|---|
| 240 V service reference | 233.7 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 119.30 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 103.8 V, below the 110 V Range B limit
A branch measurement fell without confirming movement at the 240 V service reference.
53. 2026-07-23 17:55:48 UNDERVOLTAGE
lasted 29 seconds · 30 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 104.39 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 104.39 V / 123.44 V (19.05 V split) |
|---|
| 240 V service reference | 224.9 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 103.00 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 104.4 V, below the 110 V Range B limit
- independent Ting sensor 103.0 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
54. 2026-07-23 09:18:36 UNDERVOLTAGE
lasted 11 seconds · 12 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 107.91 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 107.99 V / 123.06 V (15.07 V split) |
|---|
| 240 V service reference | 226.2 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 105.00 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 107.9 V, below the 110 V Range B limit
- independent Ting sensor 105.0 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
55. 2026-07-23 08:48:45 UNDERVOLTAGE
lasted 3 seconds · 3 samples out of range · outside Range A
LOCAL/BRANCH DROP| Lowest reading | 112.88 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 112.88 V / 123.17 V (10.30 V split) |
|---|
| 240 V service reference | 239.7 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 122.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 112.9 V, below the 114 V Range A limit
A branch measurement fell without confirming movement at the 240 V service reference.
56. 2026-07-23 08:31:27 UNDERVOLTAGE
lasted 5 seconds · 6 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 101.78 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 101.78 V / 122.84 V (21.06 V split) |
|---|
| 240 V service reference | 225.1 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 104.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 101.8 V, below the 110 V Range B limit
- independent Ting sensor 104.1 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
57. 2026-07-23 05:37:57 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LOCAL/BRANCH DROP| Lowest reading | 108.12 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 108.12 V / 122.19 V (14.06 V split) |
|---|
| 240 V service reference | 236.3 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 121.00 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 108.1 V, below the 110 V Range B limit
A branch measurement fell without confirming movement at the 240 V service reference.
58. 2026-07-23 05:21:10 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range A
LOCAL/BRANCH DROP| Lowest reading | 112.98 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 112.98 V / 122.63 V (9.65 V split) |
|---|
| 240 V service reference | 237.3 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 121.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.0 V, below the 114 V Range A limit
A branch measurement fell without confirming movement at the 240 V service reference.
59. 2026-07-23 04:55:45 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 107.37 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 107.37 V / 122.15 V (14.78 V split) |
|---|
| 240 V service reference | 228.5 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 107.50 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 107.4 V, below the 110 V Range B limit
- independent Ting sensor 107.5 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
60. 2026-07-23 03:24:52 UNDERVOLTAGE
lasted 5 seconds · 6 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 106.93 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 106.93 V / 122.65 V (15.72 V split) |
|---|
| 240 V service reference | 230.9 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 106.80 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 106.9 V, below the 110 V Range B limit
- independent Ting sensor 106.8 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
61. 2026-07-12 21:56:44 UNDERVOLTAGE
lasted 4 minutes 2 seconds · 241 samples out of range · outside Range A
LOCAL/BRANCH DROP| Lowest reading | 113.49 V on 3D Printer - Mikes Room |
|---|
| Leg A / Leg B | 122.33 V / 113.91 V (8.42 V split) |
|---|
| 240 V service reference | 236.0 V |
|---|
| Meters affected | 3D Printer - Mikes Room, Computer and TV - Mikes Room |
|---|
Ting recorded 119.50 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.5 V, below the 114 V Range A limit
A branch measurement fell without confirming movement at the 240 V service reference.
62. 2026-07-12 21:54:56 UNDERVOLTAGE
lasted 26 seconds · 27 samples out of range · outside Range A
LOCAL/BRANCH DROP| Lowest reading | 113.92 V on 3D Printer - Mikes Room |
|---|
| Leg A / Leg B | 122.33 V / 113.91 V (8.42 V split) |
|---|
| 240 V service reference | 236.0 V |
|---|
| Meters affected | 3D Printer - Mikes Room |
|---|
Ting recorded 119.50 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
A branch measurement fell without confirming movement at the 240 V service reference.
63. 2026-07-12 21:52:30 UNDERVOLTAGE
lasted 1 minute 4 seconds · 65 samples out of range · outside Range A
LOCAL/BRANCH DROP| Lowest reading | 113.68 V on 3D Printer - Mikes Room |
|---|
| Leg A / Leg B | 122.33 V / 113.91 V (8.42 V split) |
|---|
| 240 V service reference | 236.0 V |
|---|
| Meters affected | Computer and TV - Mikes Room, 3D Printer - Mikes Room |
|---|
Ting recorded 119.50 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.7 V, below the 114 V Range A limit
A branch measurement fell without confirming movement at the 240 V service reference.
64. 2026-07-05 20:19:01 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 104.65 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 104.65 V / 120.52 V (15.86 V split) |
|---|
| 240 V service reference | 225.6 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 104.80 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 104.7 V, below the 110 V Range B limit
- independent Ting sensor 104.8 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
65. 2026-07-05 20:18:34 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range A
LEG A SUPPLY SAG| Lowest reading | 110.91 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 104.65 V / 120.52 V (15.86 V split) |
|---|
| 240 V service reference | 225.6 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
Ting recorded 104.80 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 110.9 V, below the 114 V Range A limit
- independent Ting sensor 104.8 V
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
66. 2026-07-05 19:38:41 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range A
LOCAL/BRANCH DROP| Lowest reading | 113.69 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 113.69 V / 120.54 V (6.85 V split) |
|---|
| 240 V service reference | 232.7 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 113.7 V, below the 114 V Range A limit
A branch measurement fell without confirming movement at the 240 V service reference.
67. 2026-07-05 19:35:32 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LOCAL/BRANCH DROP| Lowest reading | 107.48 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 107.48 V / 120.50 V (13.02 V split) |
|---|
| 240 V service reference | 229.7 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 107.5 V, below the 110 V Range B limit
A branch measurement fell without confirming movement at the 240 V service reference.
68. 2026-07-05 19:02:14 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range A
LOCAL/BRANCH DROP| Lowest reading | 113.89 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 113.89 V / 121.02 V (7.12 V split) |
|---|
| 240 V service reference | 231.0 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 113.9 V, below the 114 V Range A limit
A branch measurement fell without confirming movement at the 240 V service reference.
69. 2026-07-05 17:43:01 UNDERVOLTAGE
lasted 2 seconds · 2 samples out of range · outside Range A
LEG A SAG| Lowest reading | 112.45 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 112.45 V / 121.44 V (8.99 V split) |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 112.5 V, below the 114 V Range A limit
The Leg A measurement fell well below its calm baseline and further than Leg B; no independent 240 V or Ting reading was available to corroborate it.
70. 2026-07-03 05:49:53 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LOCAL/BRANCH DROP| Lowest reading | 106.80 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 106.80 V / 120.85 V (14.05 V split) |
|---|
| 240 V service reference | 231.6 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 106.8 V, below the 110 V Range B limit
A branch measurement fell without confirming movement at the 240 V service reference.
71. 2026-07-03 00:41:36 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 103.16 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 103.16 V / 120.73 V (17.57 V split) |
|---|
| 240 V service reference | 226.4 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 103.2 V, below the 110 V Range B limit
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
72. 2026-07-02 23:41:13 UNDERVOLTAGE
lasted 5 seconds · 6 samples out of range · outside Range B
LOCAL/BRANCH DROP| Lowest reading | 105.10 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 105.10 V / 121.94 V (16.84 V split) |
|---|
| 240 V service reference | 233.7 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 105.1 V, below the 110 V Range B limit
A branch measurement fell without confirming movement at the 240 V service reference.
73. 2026-07-02 23:00:24 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 104.22 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 104.22 V / 121.06 V (16.84 V split) |
|---|
| 240 V service reference | 225.7 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 104.2 V, below the 110 V Range B limit
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
74. 2026-07-02 22:50:13 UNDERVOLTAGE
lasted 1 second · 2 samples out of range · outside Range A
LOCAL/BRANCH DROP| Lowest reading | 110.46 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 110.46 V / 120.98 V (10.52 V split) |
|---|
| 240 V service reference | 234.9 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 110.5 V, below the 114 V Range A limit
A branch measurement fell without confirming movement at the 240 V service reference.
75. 2026-07-02 22:38:10 UNDERVOLTAGE
lasted 7 seconds · 6 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 104.55 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 104.55 V / 120.78 V (16.23 V split) |
|---|
| 240 V service reference | 228.6 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 104.5 V, below the 110 V Range B limit
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
76. 2026-07-02 22:34:27 UNDERVOLTAGE
lasted 8 seconds · 8 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 104.20 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 104.20 V / 120.87 V (16.67 V split) |
|---|
| 240 V service reference | 220.3 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 104.2 V, below the 110 V Range B limit
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
77. 2026-07-02 22:29:54 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range A
LEG A SUPPLY SAG| Lowest reading | 112.49 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 112.49 V / 120.73 V (8.25 V split) |
|---|
| 240 V service reference | 228.4 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 112.5 V, below the 114 V Range A limit
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
78. 2026-07-02 22:22:27 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 106.19 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 106.19 V / 120.59 V (14.40 V split) |
|---|
| 240 V service reference | 230.0 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 106.2 V, below the 110 V Range B limit
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
79. 2026-07-02 22:17:27 UNDERVOLTAGE
lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 105.58 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 105.58 V / 120.64 V (15.06 V split) |
|---|
| 240 V service reference | 230.5 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 105.6 V, below the 110 V Range B limit
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
80. 2026-07-02 20:40:00 UNDERVOLTAGE
lasted 8 seconds · 4 samples out of range · outside Range A
LOCAL/BRANCH DROP| Lowest reading | 111.82 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 111.82 V / 121.02 V (9.20 V split) |
|---|
| 240 V service reference | 232.8 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 111.8 V, below the 114 V Range A limit
A branch measurement fell without confirming movement at the 240 V service reference.
81. 2026-07-02 20:09:33 UNDERVOLTAGE
lasted 4 seconds · 3 samples out of range · outside Range B
LOCAL/BRANCH DROP| Lowest reading | 108.62 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 108.62 V / 120.43 V (11.81 V split) |
|---|
| 240 V service reference | 231.8 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 108.6 V, below the 110 V Range B limit
A branch measurement fell without confirming movement at the 240 V service reference.
82. 2026-07-02 19:52:17 UNDERVOLTAGE
lasted 0 seconds · 1 sample out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 108.76 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 108.76 V / 120.59 V (11.83 V split) |
|---|
| 240 V service reference | 231.6 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 108.8 V, below the 110 V Range B limit
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
83. 2026-07-02 18:36:22 UNDERVOLTAGE
lasted 4 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG| Lowest reading | 106.54 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 106.54 V / 121.69 V (15.15 V split) |
|---|
| 240 V service reference | 224.4 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 106.5 V, below the 110 V Range B limit
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
84. 2026-07-02 10:21:57 UNDERVOLTAGE
lasted 8 seconds · 5 samples out of range · outside Range A
LEG A SUPPLY SAG| Lowest reading | 113.00 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 113.00 V / 123.21 V (10.21 V split) |
|---|
| 240 V service reference | 231.2 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 113.0 V, below the 114 V Range A limit
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
85. 2026-07-02 10:21:45 UNDERVOLTAGE
lasted 2 seconds · 2 samples out of range · outside Range A
LEG A SUPPLY SAG| Lowest reading | 113.65 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 113.00 V / 123.21 V (10.21 V split) |
|---|
| 240 V service reference | 231.2 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 113.7 V, below the 114 V Range A limit
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
86. 2026-07-02 05:49:32 UNDERVOLTAGE
lasted 0 seconds · 1 sample out of range · outside Range A
LOCAL/BRANCH DROP| Lowest reading | 113.04 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 113.04 V / 119.81 V (6.77 V split) |
|---|
| 240 V service reference | 233.6 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 113.0 V, below the 114 V Range A limit
A branch measurement fell without confirming movement at the 240 V service reference.
87. 2026-07-01 19:16:32 UNDERVOLTAGE
lasted 2 seconds · 2 samples out of range · outside Range B
LOCAL/BRANCH DROP| Lowest reading | 108.59 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 108.59 V / 120.25 V (11.66 V split) |
|---|
| 240 V service reference | 232.0 V |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 108.6 V, below the 110 V Range B limit
A branch measurement fell without confirming movement at the 240 V service reference.
88. 2026-06-30 08:57:51 UNDERVOLTAGE
lasted 0 seconds · 1 sample out of range · outside Range A
LEG A SAG| Lowest reading | 111.96 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 110.59 V / 119.96 V (9.37 V split) |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 112.0 V, below the 114 V Range A limit
The Leg A measurement fell well below its calm baseline and further than Leg B; no independent 240 V or Ting reading was available to corroborate it.
89. 2026-06-30 08:57:35 UNDERVOLTAGE
lasted 8 seconds · 4 samples out of range · outside Range A
LEG A SAG| Lowest reading | 110.59 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 110.59 V / 119.96 V (9.37 V split) |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 110.6 V, below the 114 V Range A limit
The Leg A measurement fell well below its calm baseline and further than Leg B; no independent 240 V or Ting reading was available to corroborate it.
90. 2026-06-30 08:57:21 UNDERVOLTAGE
lasted 0 seconds · 1 sample out of range · outside Range A
LEG A SAG| Lowest reading | 112.71 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 110.59 V / 119.96 V (9.37 V split) |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 112.7 V, below the 114 V Range A limit
The Leg A measurement fell well below its calm baseline and further than Leg B; no independent 240 V or Ting reading was available to corroborate it.
91. 2026-06-30 08:54:04 UNDERVOLTAGE
lasted 0 seconds · 1 sample out of range · outside Range A
LEG A SAG| Lowest reading | 110.34 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 107.06 V / 121.02 V (13.96 V split) |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 110.3 V, below the 114 V Range A limit
The Leg A measurement fell well below its calm baseline and further than Leg B; no independent 240 V or Ting reading was available to corroborate it.
92. 2026-06-30 08:52:56 UNDERVOLTAGE
lasted 0 seconds · 1 sample out of range · outside Range A
LEG A SAG| Lowest reading | 113.50 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 107.06 V / 121.02 V (13.96 V split) |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 113.5 V, below the 114 V Range A limit
The Leg A measurement fell well below its calm baseline and further than Leg B; no independent 240 V or Ting reading was available to corroborate it.
93. 2026-06-30 08:52:22 UNDERVOLTAGE
lasted 2 seconds · 2 samples out of range · outside Range B
LEG A SAG| Lowest reading | 107.06 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 107.06 V / 121.02 V (13.96 V split) |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 107.1 V, below the 110 V Range B limit
The Leg A measurement fell well below its calm baseline and further than Leg B; no independent 240 V or Ting reading was available to corroborate it.
94. 2026-06-30 08:52:10 UNDERVOLTAGE
lasted 2 seconds · 2 samples out of range · outside Range A
LEG A SAG| Lowest reading | 113.02 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 107.06 V / 121.02 V (13.96 V split) |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 113.0 V, below the 114 V Range A limit
The Leg A measurement fell well below its calm baseline and further than Leg B; no independent 240 V or Ting reading was available to corroborate it.
95. 2026-06-30 08:52:02 UNDERVOLTAGE
lasted 0 seconds · 1 sample out of range · outside Range B
LEG A SAG| Lowest reading | 109.23 V on Ubiquiti/TeslaMate Pi |
|---|
| Leg A / Leg B | 107.06 V / 121.02 V (13.96 V split) |
|---|
| Meters affected | Ubiquiti/TeslaMate Pi |
|---|
No independent Ting reading was recorded inside this window.
- branch meter 109.2 V, below the 110 V Range B limit
The Leg A measurement fell well below its calm baseline and further than Leg B; no independent 240 V or Ting reading was available to corroborate it.