Voltage Irregularity Report

Brieske residence, Orcutt CA · Since PG&E's monitor went up · Mon Aug 17, 1:00 PM to Sun Nov 22, 8:11 AM · generated 2026-11-22 08:11:43 PST

Since PG&E's monitor went up24 hours3 days7 days14 days30 daysAll time

leave “to” blank for “up to now”

☰ Simple one-page versionDownload .txtDownload .csvPrint / save PDF

Measurement method: three TP-Link EP25 metering outlets record true-RMS line voltage once per second on both 120 V legs of the split-phase service. A Tesla Wall Connector supplies the 240 V line-to-line reference and grid frequency, which is independent of the neutral. A Ting (Whisker) sensor on Leg A samples far faster than 1 Hz and retains the lowest and highest voltage it sees, so it resolves brief excursions that a 1 s RMS average necessarily flattens in both directions. Where the two disagree, the Ting figure is the closer estimate of the real extreme. What is listed: any reading below 114 V (the ANSI C84.1 Range A lower limit) and any reading above 127 V (the Range B upper limit) at 120 V nominal. Undervoltage dims and stalls equipment; sustained overvoltage damages it, so both are reported.

13,487 samples logged today across 147 retained detail files.

Also recorded but not listed individually: 34 brief high readings on a 120 V branch meter, peaking at 127.4 V. These are held back for two reasons: readings between 126 V and 127 V are inside ANSI Range B, which the standard tolerates as occasional; and none of them were confirmed by the neutral-independent 240 V line-to-line reference, which never left its limits. They are reported as a count so that nothing is hidden, not because they are being claimed.

Irregularities listed
123
Low / high
123 / 0
Corroborated by Ting
120
Lowest branch meter
0.00 V
Lowest Ting reading
84.84 V
Lowest 240 V reference
221.8 V
Time out of range
1 h 31 min

When they happen

00:00 ×2   01:00 ×1   02:00 ×1   05:00 ×1   07:00 ×1   10:00 ×1   14:00 ×1   15:00 ×3   16:00 ×7   17:00 ×41   18:00 ×41   19:00 ×14   20:00 ×3   21:00 ×3   22:00 ×1   23:00 ×2

Irregularities (newest first)

1. 2026-11-06 16:25:51 UNDERVOLTAGE

lasted 24 seconds · 23 samples out of range · outside Range B
LOCAL/BRANCH DROP
Lowest reading0.00 V on 3D Printer - Mikes Room
Leg A / Leg B122.15 V  /  61.33 V  (60.82 V split)
240 V service reference239.6 V
Meters affected3D Printer - Mikes Room
No independent Ting reading was recorded inside this window.
A branch measurement fell without confirming movement at the 240 V service reference.

2. 2026-10-06 19:55:55 UNDERVOLTAGE

lasted 14 seconds · 15 samples out of range · outside Range A
MINOR LEG IMBALANCE
Lowest reading113.91 V on 3D Printer - Mikes Room
Leg A / Leg B121.09 V  /  114.99 V  (6.10 V split)
240 V service reference235.6 V
Meters affected3D Printer - Mikes Room
Ting recorded 118.00 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
The legs differed by more than the tracking threshold, but neither fell far enough below its calm baseline or below the ANSI Range A limit to count as a sag. Normal load imbalance looks like this.

3. 2026-10-06 15:00:01 UNDERVOLTAGE

lasted 3 seconds · 4 samples out of range · outside Range A
MINOR LEG IMBALANCE
Lowest reading113.97 V on 3D Printer - Mikes Room
Leg A / Leg B123.83 V  /  115.82 V  (8.01 V split)
240 V service reference239.1 V
Meters affected3D Printer - Mikes Room
Ting recorded 119.30 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
The legs differed by more than the tracking threshold, but neither fell far enough below its calm baseline or below the ANSI Range A limit to count as a sag. Normal load imbalance looks like this.

4. 2026-10-06 14:59:44 UNDERVOLTAGE

lasted 3 seconds · 4 samples out of range · outside Range A
MINOR LEG IMBALANCE
Lowest reading113.91 V on 3D Printer - Mikes Room
Leg A / Leg B123.83 V  /  115.82 V  (8.01 V split)
240 V service reference239.1 V
Meters affected3D Printer - Mikes Room
Ting recorded 119.30 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
The legs differed by more than the tracking threshold, but neither fell far enough below its calm baseline or below the ANSI Range A limit to count as a sag. Normal load imbalance looks like this.

5. 2026-10-06 00:00:17 UNDERVOLTAGE

lasted 3 seconds · 4 samples out of range · outside Range A
MINOR LEG IMBALANCE
Lowest reading113.59 V on Computer and TV - Mikes Room
Leg A / Leg B120.94 V  /  116.67 V  (4.27 V split)
240 V service reference236.7 V
Meters affectedComputer and TV - Mikes Room
Ting recorded 119.80 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
The legs differed by more than the tracking threshold, but neither fell far enough below its calm baseline or below the ANSI Range A limit to count as a sag. Normal load imbalance looks like this.

6. 2026-10-05 20:07:35 UNDERVOLTAGE

lasted 24 minutes 15 seconds · 1450 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading112.59 V on 3D Printer - Mikes Room
Leg A / Leg B123.16 V  /  115.37 V  (7.79 V split)
240 V service reference237.4 V
Meters affected3D Printer - Mikes Room, Computer and TV - Mikes Room
Ting recorded 115.00 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

7. 2026-10-05 20:07:24 UNDERVOLTAGE

lasted 3 seconds · 4 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.99 V on 3D Printer - Mikes Room
Leg A / Leg B123.16 V  /  115.37 V  (7.79 V split)
240 V service reference237.4 V
Meters affected3D Printer - Mikes Room
Ting recorded 115.00 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

8. 2026-10-05 20:02:24 UNDERVOLTAGE

lasted 2 seconds · 3 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.92 V on 3D Printer - Mikes Room
Leg A / Leg B123.16 V  /  115.37 V  (7.79 V split)
240 V service reference237.4 V
Meters affected3D Printer - Mikes Room
Ting recorded 115.00 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

9. 2026-10-05 19:42:36 UNDERVOLTAGE

lasted 3 seconds · 4 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.45 V on 3D Printer - Mikes Room
Leg A / Leg B123.16 V  /  115.37 V  (7.79 V split)
240 V service reference237.4 V
Meters affected3D Printer - Mikes Room
Ting recorded 115.00 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

10. 2026-10-05 19:14:28 UNDERVOLTAGE

lasted 4 seconds · 5 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.98 V on 3D Printer - Mikes Room
Leg A / Leg B123.16 V  /  115.37 V  (7.79 V split)
240 V service reference237.4 V
Meters affected3D Printer - Mikes Room
Ting recorded 115.00 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

11. 2026-10-05 19:14:00 UNDERVOLTAGE

lasted 3 seconds · 4 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.99 V on 3D Printer - Mikes Room
Leg A / Leg B123.16 V  /  115.37 V  (7.79 V split)
240 V service reference237.4 V
Meters affected3D Printer - Mikes Room
Ting recorded 115.00 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

12. 2026-10-05 19:13:44 UNDERVOLTAGE

lasted 3 seconds · 4 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.98 V on 3D Printer - Mikes Room
Leg A / Leg B123.16 V  /  115.37 V  (7.79 V split)
240 V service reference237.4 V
Meters affected3D Printer - Mikes Room
Ting recorded 115.00 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

13. 2026-10-05 19:13:16 UNDERVOLTAGE

lasted 4 seconds · 5 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.99 V on 3D Printer - Mikes Room
Leg A / Leg B123.16 V  /  115.37 V  (7.79 V split)
240 V service reference237.4 V
Meters affected3D Printer - Mikes Room
Ting recorded 115.00 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

14. 2026-10-05 19:12:49 UNDERVOLTAGE

lasted 13 seconds · 14 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.94 V on 3D Printer - Mikes Room
Leg A / Leg B123.16 V  /  115.37 V  (7.79 V split)
240 V service reference237.4 V
Meters affected3D Printer - Mikes Room
Ting recorded 115.00 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

15. 2026-10-05 19:12:18 UNDERVOLTAGE

lasted 3 seconds · 4 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.98 V on 3D Printer - Mikes Room
Leg A / Leg B123.16 V  /  115.37 V  (7.79 V split)
240 V service reference237.4 V
Meters affected3D Printer - Mikes Room
Ting recorded 115.00 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

16. 2026-10-05 19:11:54 UNDERVOLTAGE

lasted 13 seconds · 14 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.75 V on 3D Printer - Mikes Room
Leg A / Leg B123.16 V  /  115.37 V  (7.79 V split)
240 V service reference237.4 V
Meters affected3D Printer - Mikes Room, Computer and TV - Mikes Room
Ting recorded 115.00 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

17. 2026-10-05 19:09:46 UNDERVOLTAGE

lasted 13 seconds · 14 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.90 V on 3D Printer - Mikes Room
Leg A / Leg B123.16 V  /  115.37 V  (7.79 V split)
240 V service reference237.4 V
Meters affected3D Printer - Mikes Room
Ting recorded 115.00 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

18. 2026-10-05 19:09:36 UNDERVOLTAGE

lasted 4 seconds · 5 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.98 V on 3D Printer - Mikes Room
Leg A / Leg B123.16 V  /  115.37 V  (7.79 V split)
240 V service reference237.4 V
Meters affected3D Printer - Mikes Room
Ting recorded 115.00 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

19. 2026-10-05 19:03:12 UNDERVOLTAGE

lasted 3 seconds · 4 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.89 V on 3D Printer - Mikes Room
Leg A / Leg B123.16 V  /  115.37 V  (7.79 V split)
240 V service reference237.4 V
Meters affected3D Printer - Mikes Room
Ting recorded 115.00 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

20. 2026-10-05 18:27:47 UNDERVOLTAGE

lasted 27 seconds · 28 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.22 V on 3D Printer - Mikes Room
Leg A / Leg B123.16 V  /  115.37 V  (7.79 V split)
240 V service reference237.4 V
Meters affectedComputer and TV - Mikes Room, 3D Printer - Mikes Room
Ting recorded 113.27 V during this event
retained low 2026-10-05 18:27:52 = 113.27 V (exact timestamp)
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

21. 2026-10-04 18:59:15 UNDERVOLTAGE

lasted 4 seconds · 5 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.96 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

22. 2026-10-04 18:58:00 UNDERVOLTAGE

lasted 1 minute 3 seconds · 64 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.79 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

23. 2026-10-04 18:57:43 UNDERVOLTAGE

lasted 0 seconds · 1 sample out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.87 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

24. 2026-10-04 18:57:20 UNDERVOLTAGE

lasted 16 seconds · 15 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.74 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

25. 2026-10-04 18:56:26 UNDERVOLTAGE

lasted 41 seconds · 40 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.84 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

26. 2026-10-04 18:55:18 UNDERVOLTAGE

lasted 3 seconds · 4 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.99 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

27. 2026-10-04 18:54:31 UNDERVOLTAGE

lasted 37 seconds · 38 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.79 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

28. 2026-10-04 18:54:24 UNDERVOLTAGE

lasted 2 seconds · 3 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.92 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

29. 2026-10-04 18:54:17 UNDERVOLTAGE

lasted 2 seconds · 3 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.94 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

30. 2026-10-04 18:53:35 UNDERVOLTAGE

lasted 34 seconds · 32 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.89 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

31. 2026-10-04 18:53:23 UNDERVOLTAGE

lasted 3 seconds · 4 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.98 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

32. 2026-10-04 18:53:02 UNDERVOLTAGE

lasted 10 seconds · 11 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.61 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room, Computer and TV - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

33. 2026-10-04 18:50:09 UNDERVOLTAGE

lasted 2 minutes 20 seconds · 139 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.11 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room, Computer and TV - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

34. 2026-10-04 18:47:38 UNDERVOLTAGE

lasted 12 seconds · 13 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.90 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

35. 2026-10-04 18:46:56 UNDERVOLTAGE

lasted 19 seconds · 17 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.92 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

36. 2026-10-04 18:46:12 UNDERVOLTAGE

lasted 38 seconds · 39 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.84 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

37. 2026-10-04 18:45:19 UNDERVOLTAGE

lasted 48 seconds · 49 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.87 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

38. 2026-10-04 18:44:27 UNDERVOLTAGE

lasted 47 seconds · 48 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.72 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room, Computer and TV - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

39. 2026-10-04 18:44:20 UNDERVOLTAGE

lasted 2 seconds · 3 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.87 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

40. 2026-10-04 18:44:02 UNDERVOLTAGE

lasted 8 seconds · 9 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.89 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

41. 2026-10-04 18:40:35 UNDERVOLTAGE

lasted 3 minutes 18 seconds · 198 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.62 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affectedComputer and TV - Mikes Room, 3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

42. 2026-10-04 18:36:36 UNDERVOLTAGE

lasted 33 seconds · 34 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.88 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

43. 2026-10-04 18:35:32 UNDERVOLTAGE

lasted 55 seconds · 51 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.87 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

44. 2026-10-04 18:35:20 UNDERVOLTAGE

lasted 3 seconds · 4 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.99 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

45. 2026-10-04 18:35:02 UNDERVOLTAGE

lasted 9 seconds · 10 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.91 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

46. 2026-10-04 18:34:52 UNDERVOLTAGE

lasted 3 seconds · 4 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.97 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

47. 2026-10-04 18:34:38 UNDERVOLTAGE

lasted 9 seconds · 10 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.95 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

48. 2026-10-04 18:33:43 UNDERVOLTAGE

lasted 46 seconds · 42 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.69 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

49. 2026-10-04 18:32:57 UNDERVOLTAGE

lasted 36 seconds · 34 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.89 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

50. 2026-10-04 18:31:44 UNDERVOLTAGE

lasted 35 seconds · 32 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.89 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

51. 2026-10-04 18:31:34 UNDERVOLTAGE

lasted 4 seconds · 5 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.94 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

52. 2026-10-04 18:31:07 UNDERVOLTAGE

lasted 0 seconds · 1 sample out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.92 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

53. 2026-10-04 18:30:59 UNDERVOLTAGE

lasted 3 seconds · 4 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.94 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

54. 2026-10-04 18:30:43 UNDERVOLTAGE

lasted 4 seconds · 5 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.98 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

55. 2026-10-04 18:30:18 UNDERVOLTAGE

lasted 3 seconds · 4 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.96 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

56. 2026-10-04 18:27:39 UNDERVOLTAGE

lasted 1 minute 53 seconds · 114 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.71 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room, Computer and TV - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

57. 2026-10-04 18:27:25 UNDERVOLTAGE

lasted 9 seconds · 10 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.80 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

58. 2026-10-04 18:26:15 UNDERVOLTAGE

lasted 1 minute 2 seconds · 62 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.64 V on 3D Printer - Mikes Room
Leg A / Leg B120.47 V  /  114.44 V  (6.03 V split)
240 V service reference234.3 V
Meters affected3D Printer - Mikes Room, Computer and TV - Mikes Room
Ting recorded 117.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

59. 2026-10-04 18:17:05 UNDERVOLTAGE

lasted 8 seconds · 9 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.94 V on 3D Printer - Mikes Room
Leg A / Leg B123.29 V  /  114.77 V  (8.52 V split)
240 V service reference237.9 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

60. 2026-10-04 17:41:00 UNDERVOLTAGE

lasted 2 seconds · 3 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.95 V on 3D Printer - Mikes Room
Leg A / Leg B123.29 V  /  114.77 V  (8.52 V split)
240 V service reference237.9 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

61. 2026-10-04 17:40:34 UNDERVOLTAGE

lasted 21 seconds · 22 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.85 V on 3D Printer - Mikes Room
Leg A / Leg B123.29 V  /  114.77 V  (8.52 V split)
240 V service reference237.9 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

62. 2026-10-04 17:39:34 UNDERVOLTAGE

lasted 48 seconds · 49 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.78 V on 3D Printer - Mikes Room
Leg A / Leg B123.29 V  /  114.77 V  (8.52 V split)
240 V service reference237.9 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

63. 2026-10-04 17:39:23 UNDERVOLTAGE

lasted 2 seconds · 3 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.95 V on 3D Printer - Mikes Room
Leg A / Leg B123.29 V  /  114.77 V  (8.52 V split)
240 V service reference237.9 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

64. 2026-10-04 17:39:07 UNDERVOLTAGE

lasted 11 seconds · 11 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.80 V on 3D Printer - Mikes Room
Leg A / Leg B123.29 V  /  114.77 V  (8.52 V split)
240 V service reference237.9 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

65. 2026-10-04 17:17:08 UNDERVOLTAGE

lasted 14 minutes 35 seconds · 873 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading112.31 V on 3D Printer - Mikes Room
Leg A / Leg B123.29 V  /  114.77 V  (8.52 V split)
240 V service reference237.9 V
Meters affectedComputer and TV - Mikes Room, 3D Printer - Mikes Room
Ting recorded 117.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

66. 2026-10-04 17:14:51 UNDERVOLTAGE

lasted 2 minutes 13 seconds · 126 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.39 V on 3D Printer - Mikes Room
Leg A / Leg B123.29 V  /  114.77 V  (8.52 V split)
240 V service reference237.9 V
Meters affectedComputer and TV - Mikes Room, 3D Printer - Mikes Room
Ting recorded 117.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

67. 2026-10-04 17:14:08 UNDERVOLTAGE

lasted 36 seconds · 37 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.46 V on 3D Printer - Mikes Room
Leg A / Leg B123.29 V  /  114.77 V  (8.52 V split)
240 V service reference237.9 V
Meters affected3D Printer - Mikes Room, Computer and TV - Mikes Room
Ting recorded 117.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

68. 2026-10-04 17:12:45 UNDERVOLTAGE

lasted 5 seconds · 6 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.84 V on 3D Printer - Mikes Room
Leg A / Leg B123.29 V  /  114.77 V  (8.52 V split)
240 V service reference237.9 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

69. 2026-10-04 17:12:09 UNDERVOLTAGE

lasted 9 seconds · 10 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.95 V on 3D Printer - Mikes Room
Leg A / Leg B123.29 V  /  114.77 V  (8.52 V split)
240 V service reference237.9 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

70. 2026-10-04 17:11:56 UNDERVOLTAGE

lasted 2 seconds · 3 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.95 V on 3D Printer - Mikes Room
Leg A / Leg B123.29 V  /  114.77 V  (8.52 V split)
240 V service reference237.9 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

71. 2026-10-04 17:11:47 UNDERVOLTAGE

lasted 4 seconds · 5 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.98 V on 3D Printer - Mikes Room
Leg A / Leg B123.29 V  /  114.77 V  (8.52 V split)
240 V service reference237.9 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

72. 2026-10-04 17:08:15 UNDERVOLTAGE

lasted 23 seconds · 24 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.75 V on 3D Printer - Mikes Room
Leg A / Leg B123.29 V  /  114.77 V  (8.52 V split)
240 V service reference237.9 V
Meters affected3D Printer - Mikes Room, Computer and TV - Mikes Room
Ting recorded 117.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

73. 2026-10-04 17:05:42 UNDERVOLTAGE

lasted 32 seconds · 33 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.81 V on 3D Printer - Mikes Room
Leg A / Leg B123.29 V  /  114.77 V  (8.52 V split)
240 V service reference237.9 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

74. 2026-10-04 17:03:38 UNDERVOLTAGE

lasted 1 minute 59 seconds · 120 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.50 V on Computer and TV - Mikes Room
Leg A / Leg B123.29 V  /  114.77 V  (8.52 V split)
240 V service reference237.9 V
Meters affected3D Printer - Mikes Room, Computer and TV - Mikes Room
Ting recorded 117.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

75. 2026-10-04 17:01:58 UNDERVOLTAGE

lasted 3 seconds · 4 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.98 V on 3D Printer - Mikes Room
Leg A / Leg B123.29 V  /  114.77 V  (8.52 V split)
240 V service reference237.9 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

76. 2026-10-04 17:01:50 UNDERVOLTAGE

lasted 3 seconds · 4 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.97 V on 3D Printer - Mikes Room
Leg A / Leg B123.29 V  /  114.77 V  (8.52 V split)
240 V service reference237.9 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

77. 2026-10-04 17:01:08 UNDERVOLTAGE

lasted 11 seconds · 12 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.90 V on 3D Printer - Mikes Room
Leg A / Leg B123.29 V  /  114.77 V  (8.52 V split)
240 V service reference237.9 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

78. 2026-10-04 16:58:14 UNDERVOLTAGE

lasted 2 minutes 45 seconds · 166 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.35 V on 3D Printer - Mikes Room
Leg A / Leg B123.29 V  /  114.77 V  (8.52 V split)
240 V service reference237.9 V
Meters affected3D Printer - Mikes Room, Computer and TV - Mikes Room
Ting recorded 117.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

79. 2026-10-04 16:58:00 UNDERVOLTAGE

lasted 8 seconds · 9 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.83 V on 3D Printer - Mikes Room
Leg A / Leg B123.29 V  /  114.77 V  (8.52 V split)
240 V service reference237.9 V
Meters affected3D Printer - Mikes Room
Ting recorded 117.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

80. 2026-10-03 18:01:59 UNDERVOLTAGE

lasted 39 seconds · 40 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.68 V on 3D Printer - Mikes Room
Leg A / Leg B121.80 V  /  113.25 V  (8.55 V split)
240 V service reference235.4 V
Meters affectedComputer and TV - Mikes Room, 3D Printer - Mikes Room
Ting recorded 118.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

81. 2026-10-03 17:53:26 UNDERVOLTAGE

lasted 3 seconds · 4 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.83 V on 3D Printer - Mikes Room
Leg A / Leg B121.80 V  /  113.25 V  (8.55 V split)
240 V service reference235.4 V
Meters affected3D Printer - Mikes Room
Ting recorded 118.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

82. 2026-10-03 17:45:42 UNDERVOLTAGE

lasted 3 seconds · 4 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.91 V on 3D Printer - Mikes Room
Leg A / Leg B121.80 V  /  113.25 V  (8.55 V split)
240 V service reference235.4 V
Meters affected3D Printer - Mikes Room
Ting recorded 118.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

83. 2026-10-03 17:45:13 UNDERVOLTAGE

lasted 24 seconds · 25 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.78 V on 3D Printer - Mikes Room
Leg A / Leg B121.80 V  /  113.25 V  (8.55 V split)
240 V service reference235.4 V
Meters affected3D Printer - Mikes Room, Computer and TV - Mikes Room
Ting recorded 118.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

84. 2026-10-03 17:44:36 UNDERVOLTAGE

lasted 15 seconds · 16 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.55 V on 3D Printer - Mikes Room
Leg A / Leg B121.80 V  /  113.25 V  (8.55 V split)
240 V service reference235.4 V
Meters affectedComputer and TV - Mikes Room, 3D Printer - Mikes Room
Ting recorded 118.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

85. 2026-10-03 17:40:10 UNDERVOLTAGE

lasted 18 seconds · 18 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.13 V on 3D Printer - Mikes Room
Leg A / Leg B121.80 V  /  113.25 V  (8.55 V split)
240 V service reference235.4 V
Meters affected3D Printer - Mikes Room, Computer and TV - Mikes Room
Ting recorded 118.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

86. 2026-10-03 17:35:59 UNDERVOLTAGE

lasted 3 seconds · 4 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.99 V on 3D Printer - Mikes Room
Leg A / Leg B121.80 V  /  113.25 V  (8.55 V split)
240 V service reference235.4 V
Meters affected3D Printer - Mikes Room
Ting recorded 118.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

87. 2026-10-03 17:34:35 UNDERVOLTAGE

lasted 15 seconds · 16 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.39 V on 3D Printer - Mikes Room
Leg A / Leg B121.80 V  /  113.25 V  (8.55 V split)
240 V service reference235.4 V
Meters affected3D Printer - Mikes Room, Computer and TV - Mikes Room
Ting recorded 118.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

88. 2026-10-03 17:33:14 UNDERVOLTAGE

lasted 3 seconds · 4 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.95 V on 3D Printer - Mikes Room
Leg A / Leg B121.80 V  /  113.25 V  (8.55 V split)
240 V service reference235.4 V
Meters affected3D Printer - Mikes Room
Ting recorded 118.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

89. 2026-10-03 17:32:45 UNDERVOLTAGE

lasted 24 seconds · 25 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.25 V on 3D Printer - Mikes Room
Leg A / Leg B121.80 V  /  113.25 V  (8.55 V split)
240 V service reference235.4 V
Meters affectedComputer and TV - Mikes Room, 3D Printer - Mikes Room
Ting recorded 118.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

90. 2026-10-03 17:29:57 UNDERVOLTAGE

lasted 55 seconds · 56 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.09 V on 3D Printer - Mikes Room
Leg A / Leg B121.80 V  /  113.25 V  (8.55 V split)
240 V service reference235.4 V
Meters affected3D Printer - Mikes Room, Computer and TV - Mikes Room
Ting recorded 118.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

91. 2026-10-03 17:27:52 UNDERVOLTAGE

lasted 51 seconds · 51 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading112.13 V on 3D Printer - Mikes Room
Leg A / Leg B121.80 V  /  113.25 V  (8.55 V split)
240 V service reference235.4 V
Meters affectedComputer and TV - Mikes Room, 3D Printer - Mikes Room
Ting recorded 118.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

92. 2026-10-03 17:27:13 UNDERVOLTAGE

lasted 33 seconds · 32 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.08 V on 3D Printer - Mikes Room
Leg A / Leg B121.80 V  /  113.25 V  (8.55 V split)
240 V service reference235.4 V
Meters affectedComputer and TV - Mikes Room, 3D Printer - Mikes Room
Ting recorded 118.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

93. 2026-10-03 17:25:49 UNDERVOLTAGE

lasted 21 seconds · 18 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.06 V on 3D Printer - Mikes Room
Leg A / Leg B121.80 V  /  113.25 V  (8.55 V split)
240 V service reference235.4 V
Meters affectedComputer and TV - Mikes Room, 3D Printer - Mikes Room
Ting recorded 118.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

94. 2026-10-03 17:24:35 UNDERVOLTAGE

lasted 1 minute 8 seconds · 58 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.23 V on 3D Printer - Mikes Room
Leg A / Leg B121.80 V  /  113.25 V  (8.55 V split)
240 V service reference235.4 V
Meters affectedComputer and TV - Mikes Room, 3D Printer - Mikes Room
Ting recorded 118.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

95. 2026-10-03 17:21:37 UNDERVOLTAGE

lasted 1 minute 52 seconds · 107 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.22 V on 3D Printer - Mikes Room
Leg A / Leg B121.80 V  /  113.25 V  (8.55 V split)
240 V service reference235.4 V
Meters affected3D Printer - Mikes Room, Computer and TV - Mikes Room
Ting recorded 118.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

96. 2026-10-03 17:20:23 UNDERVOLTAGE

lasted 12 seconds · 13 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.72 V on 3D Printer - Mikes Room
Leg A / Leg B121.80 V  /  113.25 V  (8.55 V split)
240 V service reference235.4 V
Meters affected3D Printer - Mikes Room, Computer and TV - Mikes Room
Ting recorded 118.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

97. 2026-10-03 17:19:46 UNDERVOLTAGE

lasted 32 seconds · 32 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.70 V on 3D Printer - Mikes Room
Leg A / Leg B121.80 V  /  113.25 V  (8.55 V split)
240 V service reference235.4 V
Meters affectedComputer and TV - Mikes Room, 3D Printer - Mikes Room
Ting recorded 118.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

98. 2026-10-03 17:19:02 UNDERVOLTAGE

lasted 36 seconds · 36 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.58 V on 3D Printer - Mikes Room
Leg A / Leg B121.80 V  /  113.25 V  (8.55 V split)
240 V service reference235.4 V
Meters affectedComputer and TV - Mikes Room, 3D Printer - Mikes Room
Ting recorded 118.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

99. 2026-10-03 17:16:18 UNDERVOLTAGE

lasted 1 minute 43 seconds · 103 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.07 V on 3D Printer - Mikes Room
Leg A / Leg B121.80 V  /  113.25 V  (8.55 V split)
240 V service reference235.4 V
Meters affected3D Printer - Mikes Room, Computer and TV - Mikes Room
Ting recorded 118.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

100. 2026-10-03 17:15:42 UNDERVOLTAGE

lasted 31 seconds · 31 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.43 V on 3D Printer - Mikes Room
Leg A / Leg B121.80 V  /  113.25 V  (8.55 V split)
240 V service reference235.4 V
Meters affected3D Printer - Mikes Room, Computer and TV - Mikes Room
Ting recorded 118.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

101. 2026-10-03 17:11:01 UNDERVOLTAGE

lasted 3 minutes 46 seconds · 225 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.26 V on 3D Printer - Mikes Room
Leg A / Leg B121.80 V  /  113.25 V  (8.55 V split)
240 V service reference235.4 V
Meters affectedComputer and TV - Mikes Room, 3D Printer - Mikes Room
Ting recorded 118.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

102. 2026-10-03 17:10:53 UNDERVOLTAGE

lasted 3 seconds · 4 samples out of range · outside Range A
LEG B SUPPLY SAG
Lowest reading113.34 V on 3D Printer - Mikes Room
Leg A / Leg B121.80 V  /  113.25 V  (8.55 V split)
240 V service reference235.4 V
Meters affected3D Printer - Mikes Room, Computer and TV - Mikes Room
Ting recorded 118.40 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg B and the 240 V service reference fell while Leg A stayed comparatively stable.

103. 2026-09-24 05:10:59 UNDERVOLTAGE

lasted 2 seconds · 3 samples out of range · outside Range B
MINOR LEG IMBALANCE
Lowest reading109.15 V on Computer and TV - Mikes Room
Leg A / Leg B121.65 V  /  115.04 V  (6.61 V split)
240 V service reference235.1 V
Meters affectedComputer and TV - Mikes Room
No independent Ting reading was recorded inside this window.
The legs differed by more than the tracking threshold, but neither fell far enough below its calm baseline or below the ANSI Range A limit to count as a sag. Normal load imbalance looks like this.

104. 2026-09-23 00:00:22 UNDERVOLTAGE

lasted 3 seconds · 4 samples out of range · outside Range A
MINOR LEG IMBALANCE
Lowest reading113.75 V on 3D Printer - Mikes Room
Leg A / Leg B120.55 V  /  116.73 V  (3.82 V split)
240 V service reference235.9 V
Meters affected3D Printer - Mikes Room
No independent Ting reading was recorded inside this window.
The legs differed by more than the tracking threshold, but neither fell far enough below its calm baseline or below the ANSI Range A limit to count as a sag. Normal load imbalance looks like this.

105. 2026-09-01 21:15:16 UNDERVOLTAGE

lasted 2 minutes 45 seconds · 166 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.19 V on 3D Printer - Mikes Room
Leg A / Leg B120.36 V  /  113.45 V  (6.91 V split)
240 V service reference233.1 V
Meters affected3D Printer - Mikes Room, Computer and TV - Mikes Room
Ting recorded 118.50 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

106. 2026-09-01 21:14:49 UNDERVOLTAGE

lasted 7 seconds · 8 samples out of range · outside Range A
LOCAL/BRANCH DROP
Lowest reading113.96 V on 3D Printer - Mikes Room
Leg A / Leg B120.36 V  /  113.45 V  (6.91 V split)
240 V service reference233.1 V
Meters affected3D Printer - Mikes Room
Ting recorded 118.50 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

107. 2026-08-23 16:31:26 UNDERVOLTAGE

lasted 17 seconds · 18 samples out of range · outside Range B
LEG A SUPPLY SAG
Lowest reading101.20 V on Ubiquiti/TeslaMate Pi
Leg A / Leg B101.20 V  /  123.09 V  (21.89 V split)
240 V service reference221.8 V
Meters affectedUbiquiti/TeslaMate Pi
Ting recorded 84.84 V during this event
retained 2026-08-23 16:31:25 = 84.84 V (exact timestamp)
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.

108. 2026-08-23 15:24:40 UNDERVOLTAGE

lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG
Lowest reading105.95 V on Ubiquiti/TeslaMate Pi
Leg A / Leg B105.95 V  /  121.41 V  (15.46 V split)
240 V service reference231.1 V
Meters affectedUbiquiti/TeslaMate Pi
Ting recorded 105.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.

109. 2026-08-23 15:04:33 UNDERVOLTAGE

lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG
Lowest reading106.35 V on Ubiquiti/TeslaMate Pi
Leg A / Leg B106.35 V  /  121.52 V  (15.17 V split)
240 V service reference228.8 V
Meters affectedUbiquiti/TeslaMate Pi
Ting recorded 106.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.

110. 2026-08-23 07:34:13 UNDERVOLTAGE

lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG
Lowest reading108.05 V on Ubiquiti/TeslaMate Pi
Leg A / Leg B108.05 V  /  122.30 V  (14.25 V split)
240 V service reference226.9 V
Meters affectedUbiquiti/TeslaMate Pi
Ting recorded 107.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.

111. 2026-08-23 02:20:21 UNDERVOLTAGE

lasted 11 seconds · 12 samples out of range · outside Range B
LEG A SUPPLY SAG
Lowest reading106.65 V on Ubiquiti/TeslaMate Pi
Leg A / Leg B106.65 V  /  122.51 V  (15.86 V split)
240 V service reference225.5 V
Meters affectedUbiquiti/TeslaMate Pi
Ting recorded 106.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.

112. 2026-08-23 01:52:44 UNDERVOLTAGE

lasted 2 seconds · 3 samples out of range · outside Range B
LOCAL/BRANCH DROP
Lowest reading107.02 V on Ubiquiti/TeslaMate Pi
Leg A / Leg B107.02 V  /  121.28 V  (14.27 V split)
240 V service reference231.9 V
Meters affectedUbiquiti/TeslaMate Pi
Ting recorded 119.70 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
A branch measurement fell without confirming movement at the 240 V service reference.

113. 2026-08-22 23:02:00 UNDERVOLTAGE

lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG
Lowest reading108.56 V on Ubiquiti/TeslaMate Pi
Leg A / Leg B108.56 V  /  119.57 V  (11.01 V split)
240 V service reference231.1 V
Meters affectedUbiquiti/TeslaMate Pi
Ting recorded 115.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.

114. 2026-08-22 23:01:30 UNDERVOLTAGE

lasted 2 seconds · 3 samples out of range · outside Range A
LEG A SUPPLY SAG
Lowest reading112.00 V on Ubiquiti/TeslaMate Pi
Leg A / Leg B108.56 V  /  119.57 V  (11.01 V split)
240 V service reference231.1 V
Meters affectedUbiquiti/TeslaMate Pi
Ting recorded 115.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.

115. 2026-08-22 22:28:30 UNDERVOLTAGE

lasted 2 seconds · 3 samples out of range · outside Range A
LEG A SUPPLY SAG
Lowest reading112.51 V on Ubiquiti/TeslaMate Pi
Leg A / Leg B112.51 V  /  119.12 V  (6.61 V split)
240 V service reference229.3 V
Meters affectedUbiquiti/TeslaMate Pi
Ting recorded 106.10 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.

116. 2026-08-22 21:41:20 UNDERVOLTAGE

lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG
Lowest reading107.71 V on Ubiquiti/TeslaMate Pi
Leg A / Leg B107.71 V  /  117.18 V  (9.47 V split)
240 V service reference228.2 V
Meters affectedUbiquiti/TeslaMate Pi
Ting recorded 105.70 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.

117. 2026-08-21 19:51:42 UNDERVOLTAGE

lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG
Lowest reading105.98 V on Ubiquiti/TeslaMate Pi
Leg A / Leg B105.98 V  /  122.14 V  (16.16 V split)
240 V service reference226.8 V
Meters affectedUbiquiti/TeslaMate Pi
Ting recorded 106.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.

118. 2026-08-21 19:50:57 UNDERVOLTAGE

lasted 2 seconds · 3 samples out of range · outside Range A
LEG A SUPPLY SAG
Lowest reading113.98 V on Ubiquiti/TeslaMate Pi
Leg A / Leg B105.98 V  /  122.14 V  (16.16 V split)
240 V service reference226.8 V
Meters affectedUbiquiti/TeslaMate Pi
Ting recorded 106.20 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.

119. 2026-08-21 17:19:49 UNDERVOLTAGE

lasted 11 seconds · 12 samples out of range · outside Range B
LEG A SUPPLY SAG
Lowest reading104.89 V on Ubiquiti/TeslaMate Pi
Leg A / Leg B104.89 V  /  122.97 V  (18.08 V split)
240 V service reference226.0 V
Meters affectedUbiquiti/TeslaMate Pi
Ting recorded 103.50 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.

120. 2026-08-21 16:51:39 UNDERVOLTAGE

lasted 2 seconds · 3 samples out of range · outside Range B
LEG A SUPPLY SAG
Lowest reading107.63 V on Ubiquiti/TeslaMate Pi
Leg A / Leg B107.63 V  /  121.16 V  (13.53 V split)
240 V service reference226.4 V
Meters affectedUbiquiti/TeslaMate Pi
Ting recorded 106.80 V during this event
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.

121. 2026-08-21 16:29:02 UNDERVOLTAGE

lasted 18 seconds · 18 samples out of range · outside Range B
LEG A SUPPLY SAG
Lowest reading104.01 V on Ubiquiti/TeslaMate Pi
Leg A / Leg B104.01 V  /  118.75 V  (14.73 V split)
240 V service reference222.5 V
Meters affectedUbiquiti/TeslaMate Pi
Ting recorded 86.35 V during this event
retained 2026-08-21 16:28:50 = 86.35 V (exact timestamp)
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.

122. 2026-08-21 16:28:51 UNDERVOLTAGE

lasted 5 seconds · 6 samples out of range · outside Range B
LEG A SUPPLY SAG
Lowest reading104.52 V on Ubiquiti/TeslaMate Pi
Leg A / Leg B104.01 V  /  118.75 V  (14.73 V split)
240 V service reference222.5 V
Meters affectedUbiquiti/TeslaMate Pi
Ting recorded 86.35 V during this event
retained 2026-08-21 16:28:50 = 86.35 V (exact timestamp)
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.

123. 2026-08-21 10:14:44 UNDERVOLTAGE

lasted 5 seconds · 6 samples out of range · outside Range B
LEG A SUPPLY SAG
Lowest reading104.49 V on Ubiquiti/TeslaMate Pi
Leg A / Leg B104.49 V  /  123.26 V  (18.77 V split)
240 V service reference225.9 V
Meters affectedUbiquiti/TeslaMate Pi
Ting recorded 97.71 V during this event
retained 2026-08-21 10:14:47 = 97.71 V (exact timestamp)
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
Leg A and the 240 V service reference fell while Leg B stayed comparatively stable.
Labels describe the simultaneous meter pattern. They do not assert a confirmed physical cause; that determination belongs to the utility or electrician after inspecting the service.