Voltage Irregularity Report
Brieske residence, Orcutt CA · Since PG&E's monitor went up · Mon Aug 17, 1:00 PM to Sun Nov 22, 8:11 AM · generated 2026-11-22 08:11:43 PST
Since PG&E's monitor went up24 hours3 days7 days14 days30 daysAll time
☰ Simple one-page versionDownload .txtDownload .csvPrint / save PDF
13,487 samples logged today across 147 retained detail files.
Also recorded but not listed individually: 34 brief high readings on a 120 V branch meter, peaking at 127.4 V. These are held back for two reasons: readings between 126 V and 127 V are inside ANSI Range B, which the standard tolerates as occasional; and none of them were confirmed by the neutral-independent 240 V line-to-line reference, which never left its limits. They are reported as a count so that nothing is hidden, not because they are being claimed.
When they happen
00:00 ×2 01:00 ×1 02:00 ×1 05:00 ×1 07:00 ×1 10:00 ×1 14:00 ×1 15:00 ×3 16:00 ×7 17:00 ×41 18:00 ×41 19:00 ×14 20:00 ×3 21:00 ×3 22:00 ×1 23:00 ×2
Irregularities (newest first)
1. 2026-11-06 16:25:51 UNDERVOLTAGE
| Lowest reading | 0.00 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 122.15 V / 61.33 V (60.82 V split) |
| 240 V service reference | 239.6 V |
| Meters affected | 3D Printer - Mikes Room |
- branch meter 0.0 V, below the 110 V Range B limit
2. 2026-10-06 19:55:55 UNDERVOLTAGE
| Lowest reading | 113.91 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 121.09 V / 114.99 V (6.10 V split) |
| 240 V service reference | 235.6 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
3. 2026-10-06 15:00:01 UNDERVOLTAGE
| Lowest reading | 113.97 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.83 V / 115.82 V (8.01 V split) |
| 240 V service reference | 239.1 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
4. 2026-10-06 14:59:44 UNDERVOLTAGE
| Lowest reading | 113.91 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.83 V / 115.82 V (8.01 V split) |
| 240 V service reference | 239.1 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
5. 2026-10-06 00:00:17 UNDERVOLTAGE
| Lowest reading | 113.59 V on Computer and TV - Mikes Room |
|---|---|
| Leg A / Leg B | 120.94 V / 116.67 V (4.27 V split) |
| 240 V service reference | 236.7 V |
| Meters affected | Computer and TV - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.6 V, below the 114 V Range A limit
6. 2026-10-05 20:07:35 UNDERVOLTAGE
| Lowest reading | 112.59 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.16 V / 115.37 V (7.79 V split) |
| 240 V service reference | 237.4 V |
| Meters affected | 3D Printer - Mikes Room, Computer and TV - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 112.6 V, below the 114 V Range A limit
7. 2026-10-05 20:07:24 UNDERVOLTAGE
| Lowest reading | 113.99 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.16 V / 115.37 V (7.79 V split) |
| 240 V service reference | 237.4 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
8. 2026-10-05 20:02:24 UNDERVOLTAGE
| Lowest reading | 113.92 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.16 V / 115.37 V (7.79 V split) |
| 240 V service reference | 237.4 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
9. 2026-10-05 19:42:36 UNDERVOLTAGE
| Lowest reading | 113.45 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.16 V / 115.37 V (7.79 V split) |
| 240 V service reference | 237.4 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.5 V, below the 114 V Range A limit
10. 2026-10-05 19:14:28 UNDERVOLTAGE
| Lowest reading | 113.98 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.16 V / 115.37 V (7.79 V split) |
| 240 V service reference | 237.4 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
11. 2026-10-05 19:14:00 UNDERVOLTAGE
| Lowest reading | 113.99 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.16 V / 115.37 V (7.79 V split) |
| 240 V service reference | 237.4 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
12. 2026-10-05 19:13:44 UNDERVOLTAGE
| Lowest reading | 113.98 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.16 V / 115.37 V (7.79 V split) |
| 240 V service reference | 237.4 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
13. 2026-10-05 19:13:16 UNDERVOLTAGE
| Lowest reading | 113.99 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.16 V / 115.37 V (7.79 V split) |
| 240 V service reference | 237.4 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
14. 2026-10-05 19:12:49 UNDERVOLTAGE
| Lowest reading | 113.94 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.16 V / 115.37 V (7.79 V split) |
| 240 V service reference | 237.4 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
15. 2026-10-05 19:12:18 UNDERVOLTAGE
| Lowest reading | 113.98 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.16 V / 115.37 V (7.79 V split) |
| 240 V service reference | 237.4 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
16. 2026-10-05 19:11:54 UNDERVOLTAGE
| Lowest reading | 113.75 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.16 V / 115.37 V (7.79 V split) |
| 240 V service reference | 237.4 V |
| Meters affected | 3D Printer - Mikes Room, Computer and TV - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.8 V, below the 114 V Range A limit
17. 2026-10-05 19:09:46 UNDERVOLTAGE
| Lowest reading | 113.90 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.16 V / 115.37 V (7.79 V split) |
| 240 V service reference | 237.4 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
18. 2026-10-05 19:09:36 UNDERVOLTAGE
| Lowest reading | 113.98 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.16 V / 115.37 V (7.79 V split) |
| 240 V service reference | 237.4 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
19. 2026-10-05 19:03:12 UNDERVOLTAGE
| Lowest reading | 113.89 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.16 V / 115.37 V (7.79 V split) |
| 240 V service reference | 237.4 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
20. 2026-10-05 18:27:47 UNDERVOLTAGE
| Lowest reading | 113.22 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.16 V / 115.37 V (7.79 V split) |
| 240 V service reference | 237.4 V |
| Meters affected | Computer and TV - Mikes Room, 3D Printer - Mikes Room |
retained low 2026-10-05 18:27:52 = 113.27 V (exact timestamp)
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.2 V, below the 114 V Range A limit
- independent Ting sensor 113.3 V
21. 2026-10-04 18:59:15 UNDERVOLTAGE
| Lowest reading | 113.96 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
22. 2026-10-04 18:58:00 UNDERVOLTAGE
| Lowest reading | 113.79 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.8 V, below the 114 V Range A limit
23. 2026-10-04 18:57:43 UNDERVOLTAGE
| Lowest reading | 113.87 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
24. 2026-10-04 18:57:20 UNDERVOLTAGE
| Lowest reading | 113.74 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.7 V, below the 114 V Range A limit
25. 2026-10-04 18:56:26 UNDERVOLTAGE
| Lowest reading | 113.84 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.8 V, below the 114 V Range A limit
26. 2026-10-04 18:55:18 UNDERVOLTAGE
| Lowest reading | 113.99 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
27. 2026-10-04 18:54:31 UNDERVOLTAGE
| Lowest reading | 113.79 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.8 V, below the 114 V Range A limit
28. 2026-10-04 18:54:24 UNDERVOLTAGE
| Lowest reading | 113.92 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
29. 2026-10-04 18:54:17 UNDERVOLTAGE
| Lowest reading | 113.94 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
30. 2026-10-04 18:53:35 UNDERVOLTAGE
| Lowest reading | 113.89 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
31. 2026-10-04 18:53:23 UNDERVOLTAGE
| Lowest reading | 113.98 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
32. 2026-10-04 18:53:02 UNDERVOLTAGE
| Lowest reading | 113.61 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room, Computer and TV - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.6 V, below the 114 V Range A limit
33. 2026-10-04 18:50:09 UNDERVOLTAGE
| Lowest reading | 113.11 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room, Computer and TV - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.1 V, below the 114 V Range A limit
34. 2026-10-04 18:47:38 UNDERVOLTAGE
| Lowest reading | 113.90 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
35. 2026-10-04 18:46:56 UNDERVOLTAGE
| Lowest reading | 113.92 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
36. 2026-10-04 18:46:12 UNDERVOLTAGE
| Lowest reading | 113.84 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.8 V, below the 114 V Range A limit
37. 2026-10-04 18:45:19 UNDERVOLTAGE
| Lowest reading | 113.87 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
38. 2026-10-04 18:44:27 UNDERVOLTAGE
| Lowest reading | 113.72 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room, Computer and TV - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.7 V, below the 114 V Range A limit
39. 2026-10-04 18:44:20 UNDERVOLTAGE
| Lowest reading | 113.87 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
40. 2026-10-04 18:44:02 UNDERVOLTAGE
| Lowest reading | 113.89 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
41. 2026-10-04 18:40:35 UNDERVOLTAGE
| Lowest reading | 113.62 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | Computer and TV - Mikes Room, 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.6 V, below the 114 V Range A limit
42. 2026-10-04 18:36:36 UNDERVOLTAGE
| Lowest reading | 113.88 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
43. 2026-10-04 18:35:32 UNDERVOLTAGE
| Lowest reading | 113.87 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
44. 2026-10-04 18:35:20 UNDERVOLTAGE
| Lowest reading | 113.99 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
45. 2026-10-04 18:35:02 UNDERVOLTAGE
| Lowest reading | 113.91 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
46. 2026-10-04 18:34:52 UNDERVOLTAGE
| Lowest reading | 113.97 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
47. 2026-10-04 18:34:38 UNDERVOLTAGE
| Lowest reading | 113.95 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
48. 2026-10-04 18:33:43 UNDERVOLTAGE
| Lowest reading | 113.69 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.7 V, below the 114 V Range A limit
49. 2026-10-04 18:32:57 UNDERVOLTAGE
| Lowest reading | 113.89 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
50. 2026-10-04 18:31:44 UNDERVOLTAGE
| Lowest reading | 113.89 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
51. 2026-10-04 18:31:34 UNDERVOLTAGE
| Lowest reading | 113.94 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
52. 2026-10-04 18:31:07 UNDERVOLTAGE
| Lowest reading | 113.92 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
53. 2026-10-04 18:30:59 UNDERVOLTAGE
| Lowest reading | 113.94 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
54. 2026-10-04 18:30:43 UNDERVOLTAGE
| Lowest reading | 113.98 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
55. 2026-10-04 18:30:18 UNDERVOLTAGE
| Lowest reading | 113.96 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
56. 2026-10-04 18:27:39 UNDERVOLTAGE
| Lowest reading | 113.71 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room, Computer and TV - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.7 V, below the 114 V Range A limit
57. 2026-10-04 18:27:25 UNDERVOLTAGE
| Lowest reading | 113.80 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.8 V, below the 114 V Range A limit
58. 2026-10-04 18:26:15 UNDERVOLTAGE
| Lowest reading | 113.64 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.47 V / 114.44 V (6.03 V split) |
| 240 V service reference | 234.3 V |
| Meters affected | 3D Printer - Mikes Room, Computer and TV - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.6 V, below the 114 V Range A limit
59. 2026-10-04 18:17:05 UNDERVOLTAGE
| Lowest reading | 113.94 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.29 V / 114.77 V (8.52 V split) |
| 240 V service reference | 237.9 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
60. 2026-10-04 17:41:00 UNDERVOLTAGE
| Lowest reading | 113.95 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.29 V / 114.77 V (8.52 V split) |
| 240 V service reference | 237.9 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
61. 2026-10-04 17:40:34 UNDERVOLTAGE
| Lowest reading | 113.85 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.29 V / 114.77 V (8.52 V split) |
| 240 V service reference | 237.9 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.8 V, below the 114 V Range A limit
62. 2026-10-04 17:39:34 UNDERVOLTAGE
| Lowest reading | 113.78 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.29 V / 114.77 V (8.52 V split) |
| 240 V service reference | 237.9 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.8 V, below the 114 V Range A limit
63. 2026-10-04 17:39:23 UNDERVOLTAGE
| Lowest reading | 113.95 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.29 V / 114.77 V (8.52 V split) |
| 240 V service reference | 237.9 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
64. 2026-10-04 17:39:07 UNDERVOLTAGE
| Lowest reading | 113.80 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.29 V / 114.77 V (8.52 V split) |
| 240 V service reference | 237.9 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.8 V, below the 114 V Range A limit
65. 2026-10-04 17:17:08 UNDERVOLTAGE
| Lowest reading | 112.31 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.29 V / 114.77 V (8.52 V split) |
| 240 V service reference | 237.9 V |
| Meters affected | Computer and TV - Mikes Room, 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 112.3 V, below the 114 V Range A limit
66. 2026-10-04 17:14:51 UNDERVOLTAGE
| Lowest reading | 113.39 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.29 V / 114.77 V (8.52 V split) |
| 240 V service reference | 237.9 V |
| Meters affected | Computer and TV - Mikes Room, 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.4 V, below the 114 V Range A limit
67. 2026-10-04 17:14:08 UNDERVOLTAGE
| Lowest reading | 113.46 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.29 V / 114.77 V (8.52 V split) |
| 240 V service reference | 237.9 V |
| Meters affected | 3D Printer - Mikes Room, Computer and TV - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.5 V, below the 114 V Range A limit
68. 2026-10-04 17:12:45 UNDERVOLTAGE
| Lowest reading | 113.84 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.29 V / 114.77 V (8.52 V split) |
| 240 V service reference | 237.9 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.8 V, below the 114 V Range A limit
69. 2026-10-04 17:12:09 UNDERVOLTAGE
| Lowest reading | 113.95 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.29 V / 114.77 V (8.52 V split) |
| 240 V service reference | 237.9 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
70. 2026-10-04 17:11:56 UNDERVOLTAGE
| Lowest reading | 113.95 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.29 V / 114.77 V (8.52 V split) |
| 240 V service reference | 237.9 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
71. 2026-10-04 17:11:47 UNDERVOLTAGE
| Lowest reading | 113.98 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.29 V / 114.77 V (8.52 V split) |
| 240 V service reference | 237.9 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
72. 2026-10-04 17:08:15 UNDERVOLTAGE
| Lowest reading | 113.75 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.29 V / 114.77 V (8.52 V split) |
| 240 V service reference | 237.9 V |
| Meters affected | 3D Printer - Mikes Room, Computer and TV - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.8 V, below the 114 V Range A limit
73. 2026-10-04 17:05:42 UNDERVOLTAGE
| Lowest reading | 113.81 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.29 V / 114.77 V (8.52 V split) |
| 240 V service reference | 237.9 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.8 V, below the 114 V Range A limit
74. 2026-10-04 17:03:38 UNDERVOLTAGE
| Lowest reading | 113.50 V on Computer and TV - Mikes Room |
|---|---|
| Leg A / Leg B | 123.29 V / 114.77 V (8.52 V split) |
| 240 V service reference | 237.9 V |
| Meters affected | 3D Printer - Mikes Room, Computer and TV - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.5 V, below the 114 V Range A limit
75. 2026-10-04 17:01:58 UNDERVOLTAGE
| Lowest reading | 113.98 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.29 V / 114.77 V (8.52 V split) |
| 240 V service reference | 237.9 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
76. 2026-10-04 17:01:50 UNDERVOLTAGE
| Lowest reading | 113.97 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.29 V / 114.77 V (8.52 V split) |
| 240 V service reference | 237.9 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
77. 2026-10-04 17:01:08 UNDERVOLTAGE
| Lowest reading | 113.90 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.29 V / 114.77 V (8.52 V split) |
| 240 V service reference | 237.9 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
78. 2026-10-04 16:58:14 UNDERVOLTAGE
| Lowest reading | 113.35 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.29 V / 114.77 V (8.52 V split) |
| 240 V service reference | 237.9 V |
| Meters affected | 3D Printer - Mikes Room, Computer and TV - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.3 V, below the 114 V Range A limit
79. 2026-10-04 16:58:00 UNDERVOLTAGE
| Lowest reading | 113.83 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 123.29 V / 114.77 V (8.52 V split) |
| 240 V service reference | 237.9 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.8 V, below the 114 V Range A limit
80. 2026-10-03 18:01:59 UNDERVOLTAGE
| Lowest reading | 113.68 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 121.80 V / 113.25 V (8.55 V split) |
| 240 V service reference | 235.4 V |
| Meters affected | Computer and TV - Mikes Room, 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.7 V, below the 114 V Range A limit
81. 2026-10-03 17:53:26 UNDERVOLTAGE
| Lowest reading | 113.83 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 121.80 V / 113.25 V (8.55 V split) |
| 240 V service reference | 235.4 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.8 V, below the 114 V Range A limit
82. 2026-10-03 17:45:42 UNDERVOLTAGE
| Lowest reading | 113.91 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 121.80 V / 113.25 V (8.55 V split) |
| 240 V service reference | 235.4 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.9 V, below the 114 V Range A limit
83. 2026-10-03 17:45:13 UNDERVOLTAGE
| Lowest reading | 113.78 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 121.80 V / 113.25 V (8.55 V split) |
| 240 V service reference | 235.4 V |
| Meters affected | 3D Printer - Mikes Room, Computer and TV - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.8 V, below the 114 V Range A limit
84. 2026-10-03 17:44:36 UNDERVOLTAGE
| Lowest reading | 113.55 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 121.80 V / 113.25 V (8.55 V split) |
| 240 V service reference | 235.4 V |
| Meters affected | Computer and TV - Mikes Room, 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.5 V, below the 114 V Range A limit
85. 2026-10-03 17:40:10 UNDERVOLTAGE
| Lowest reading | 113.13 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 121.80 V / 113.25 V (8.55 V split) |
| 240 V service reference | 235.4 V |
| Meters affected | 3D Printer - Mikes Room, Computer and TV - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.1 V, below the 114 V Range A limit
86. 2026-10-03 17:35:59 UNDERVOLTAGE
| Lowest reading | 113.99 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 121.80 V / 113.25 V (8.55 V split) |
| 240 V service reference | 235.4 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
87. 2026-10-03 17:34:35 UNDERVOLTAGE
| Lowest reading | 113.39 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 121.80 V / 113.25 V (8.55 V split) |
| 240 V service reference | 235.4 V |
| Meters affected | 3D Printer - Mikes Room, Computer and TV - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.4 V, below the 114 V Range A limit
88. 2026-10-03 17:33:14 UNDERVOLTAGE
| Lowest reading | 113.95 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 121.80 V / 113.25 V (8.55 V split) |
| 240 V service reference | 235.4 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
89. 2026-10-03 17:32:45 UNDERVOLTAGE
| Lowest reading | 113.25 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 121.80 V / 113.25 V (8.55 V split) |
| 240 V service reference | 235.4 V |
| Meters affected | Computer and TV - Mikes Room, 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.2 V, below the 114 V Range A limit
90. 2026-10-03 17:29:57 UNDERVOLTAGE
| Lowest reading | 113.09 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 121.80 V / 113.25 V (8.55 V split) |
| 240 V service reference | 235.4 V |
| Meters affected | 3D Printer - Mikes Room, Computer and TV - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.1 V, below the 114 V Range A limit
91. 2026-10-03 17:27:52 UNDERVOLTAGE
| Lowest reading | 112.13 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 121.80 V / 113.25 V (8.55 V split) |
| 240 V service reference | 235.4 V |
| Meters affected | Computer and TV - Mikes Room, 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 112.1 V, below the 114 V Range A limit
92. 2026-10-03 17:27:13 UNDERVOLTAGE
| Lowest reading | 113.08 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 121.80 V / 113.25 V (8.55 V split) |
| 240 V service reference | 235.4 V |
| Meters affected | Computer and TV - Mikes Room, 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.1 V, below the 114 V Range A limit
93. 2026-10-03 17:25:49 UNDERVOLTAGE
| Lowest reading | 113.06 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 121.80 V / 113.25 V (8.55 V split) |
| 240 V service reference | 235.4 V |
| Meters affected | Computer and TV - Mikes Room, 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.1 V, below the 114 V Range A limit
94. 2026-10-03 17:24:35 UNDERVOLTAGE
| Lowest reading | 113.23 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 121.80 V / 113.25 V (8.55 V split) |
| 240 V service reference | 235.4 V |
| Meters affected | Computer and TV - Mikes Room, 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.2 V, below the 114 V Range A limit
95. 2026-10-03 17:21:37 UNDERVOLTAGE
| Lowest reading | 113.22 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 121.80 V / 113.25 V (8.55 V split) |
| 240 V service reference | 235.4 V |
| Meters affected | 3D Printer - Mikes Room, Computer and TV - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.2 V, below the 114 V Range A limit
96. 2026-10-03 17:20:23 UNDERVOLTAGE
| Lowest reading | 113.72 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 121.80 V / 113.25 V (8.55 V split) |
| 240 V service reference | 235.4 V |
| Meters affected | 3D Printer - Mikes Room, Computer and TV - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.7 V, below the 114 V Range A limit
97. 2026-10-03 17:19:46 UNDERVOLTAGE
| Lowest reading | 113.70 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 121.80 V / 113.25 V (8.55 V split) |
| 240 V service reference | 235.4 V |
| Meters affected | Computer and TV - Mikes Room, 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.7 V, below the 114 V Range A limit
98. 2026-10-03 17:19:02 UNDERVOLTAGE
| Lowest reading | 113.58 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 121.80 V / 113.25 V (8.55 V split) |
| 240 V service reference | 235.4 V |
| Meters affected | Computer and TV - Mikes Room, 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.6 V, below the 114 V Range A limit
99. 2026-10-03 17:16:18 UNDERVOLTAGE
| Lowest reading | 113.07 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 121.80 V / 113.25 V (8.55 V split) |
| 240 V service reference | 235.4 V |
| Meters affected | 3D Printer - Mikes Room, Computer and TV - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.1 V, below the 114 V Range A limit
100. 2026-10-03 17:15:42 UNDERVOLTAGE
| Lowest reading | 113.43 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 121.80 V / 113.25 V (8.55 V split) |
| 240 V service reference | 235.4 V |
| Meters affected | 3D Printer - Mikes Room, Computer and TV - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.4 V, below the 114 V Range A limit
101. 2026-10-03 17:11:01 UNDERVOLTAGE
| Lowest reading | 113.26 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 121.80 V / 113.25 V (8.55 V split) |
| 240 V service reference | 235.4 V |
| Meters affected | Computer and TV - Mikes Room, 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.3 V, below the 114 V Range A limit
102. 2026-10-03 17:10:53 UNDERVOLTAGE
| Lowest reading | 113.34 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 121.80 V / 113.25 V (8.55 V split) |
| 240 V service reference | 235.4 V |
| Meters affected | 3D Printer - Mikes Room, Computer and TV - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.3 V, below the 114 V Range A limit
103. 2026-09-24 05:10:59 UNDERVOLTAGE
| Lowest reading | 109.15 V on Computer and TV - Mikes Room |
|---|---|
| Leg A / Leg B | 121.65 V / 115.04 V (6.61 V split) |
| 240 V service reference | 235.1 V |
| Meters affected | Computer and TV - Mikes Room |
- branch meter 109.2 V, below the 110 V Range B limit
104. 2026-09-23 00:00:22 UNDERVOLTAGE
| Lowest reading | 113.75 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.55 V / 116.73 V (3.82 V split) |
| 240 V service reference | 235.9 V |
| Meters affected | 3D Printer - Mikes Room |
- branch meter 113.8 V, below the 114 V Range A limit
105. 2026-09-01 21:15:16 UNDERVOLTAGE
| Lowest reading | 113.19 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.36 V / 113.45 V (6.91 V split) |
| 240 V service reference | 233.1 V |
| Meters affected | 3D Printer - Mikes Room, Computer and TV - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 113.2 V, below the 114 V Range A limit
106. 2026-09-01 21:14:49 UNDERVOLTAGE
| Lowest reading | 113.96 V on 3D Printer - Mikes Room |
|---|---|
| Leg A / Leg B | 120.36 V / 113.45 V (6.91 V split) |
| 240 V service reference | 233.1 V |
| Meters affected | 3D Printer - Mikes Room |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
107. 2026-08-23 16:31:26 UNDERVOLTAGE
| Lowest reading | 101.20 V on Ubiquiti/TeslaMate Pi |
|---|---|
| Leg A / Leg B | 101.20 V / 123.09 V (21.89 V split) |
| 240 V service reference | 221.8 V |
| Meters affected | Ubiquiti/TeslaMate Pi |
retained 2026-08-23 16:31:25 = 84.84 V (exact timestamp)
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 101.2 V, below the 110 V Range B limit
- independent Ting sensor 84.8 V
108. 2026-08-23 15:24:40 UNDERVOLTAGE
| Lowest reading | 105.95 V on Ubiquiti/TeslaMate Pi |
|---|---|
| Leg A / Leg B | 105.95 V / 121.41 V (15.46 V split) |
| 240 V service reference | 231.1 V |
| Meters affected | Ubiquiti/TeslaMate Pi |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 106.0 V, below the 110 V Range B limit
- independent Ting sensor 105.2 V
109. 2026-08-23 15:04:33 UNDERVOLTAGE
| Lowest reading | 106.35 V on Ubiquiti/TeslaMate Pi |
|---|---|
| Leg A / Leg B | 106.35 V / 121.52 V (15.17 V split) |
| 240 V service reference | 228.8 V |
| Meters affected | Ubiquiti/TeslaMate Pi |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 106.3 V, below the 110 V Range B limit
- independent Ting sensor 106.1 V
110. 2026-08-23 07:34:13 UNDERVOLTAGE
| Lowest reading | 108.05 V on Ubiquiti/TeslaMate Pi |
|---|---|
| Leg A / Leg B | 108.05 V / 122.30 V (14.25 V split) |
| 240 V service reference | 226.9 V |
| Meters affected | Ubiquiti/TeslaMate Pi |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 108.0 V, below the 110 V Range B limit
- independent Ting sensor 107.2 V
111. 2026-08-23 02:20:21 UNDERVOLTAGE
| Lowest reading | 106.65 V on Ubiquiti/TeslaMate Pi |
|---|---|
| Leg A / Leg B | 106.65 V / 122.51 V (15.86 V split) |
| 240 V service reference | 225.5 V |
| Meters affected | Ubiquiti/TeslaMate Pi |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 106.7 V, below the 110 V Range B limit
- independent Ting sensor 106.1 V
112. 2026-08-23 01:52:44 UNDERVOLTAGE
| Lowest reading | 107.02 V on Ubiquiti/TeslaMate Pi |
|---|---|
| Leg A / Leg B | 107.02 V / 121.28 V (14.27 V split) |
| 240 V service reference | 231.9 V |
| Meters affected | Ubiquiti/TeslaMate Pi |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 107.0 V, below the 110 V Range B limit
113. 2026-08-22 23:02:00 UNDERVOLTAGE
| Lowest reading | 108.56 V on Ubiquiti/TeslaMate Pi |
|---|---|
| Leg A / Leg B | 108.56 V / 119.57 V (11.01 V split) |
| 240 V service reference | 231.1 V |
| Meters affected | Ubiquiti/TeslaMate Pi |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 108.6 V, below the 110 V Range B limit
114. 2026-08-22 23:01:30 UNDERVOLTAGE
| Lowest reading | 112.00 V on Ubiquiti/TeslaMate Pi |
|---|---|
| Leg A / Leg B | 108.56 V / 119.57 V (11.01 V split) |
| 240 V service reference | 231.1 V |
| Meters affected | Ubiquiti/TeslaMate Pi |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 112.0 V, below the 114 V Range A limit
115. 2026-08-22 22:28:30 UNDERVOLTAGE
| Lowest reading | 112.51 V on Ubiquiti/TeslaMate Pi |
|---|---|
| Leg A / Leg B | 112.51 V / 119.12 V (6.61 V split) |
| 240 V service reference | 229.3 V |
| Meters affected | Ubiquiti/TeslaMate Pi |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 112.5 V, below the 114 V Range A limit
- independent Ting sensor 106.1 V
116. 2026-08-22 21:41:20 UNDERVOLTAGE
| Lowest reading | 107.71 V on Ubiquiti/TeslaMate Pi |
|---|---|
| Leg A / Leg B | 107.71 V / 117.18 V (9.47 V split) |
| 240 V service reference | 228.2 V |
| Meters affected | Ubiquiti/TeslaMate Pi |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 107.7 V, below the 110 V Range B limit
- independent Ting sensor 105.7 V
117. 2026-08-21 19:51:42 UNDERVOLTAGE
| Lowest reading | 105.98 V on Ubiquiti/TeslaMate Pi |
|---|---|
| Leg A / Leg B | 105.98 V / 122.14 V (16.16 V split) |
| 240 V service reference | 226.8 V |
| Meters affected | Ubiquiti/TeslaMate Pi |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 106.0 V, below the 110 V Range B limit
- independent Ting sensor 106.2 V
118. 2026-08-21 19:50:57 UNDERVOLTAGE
| Lowest reading | 113.98 V on Ubiquiti/TeslaMate Pi |
|---|---|
| Leg A / Leg B | 105.98 V / 122.14 V (16.16 V split) |
| 240 V service reference | 226.8 V |
| Meters affected | Ubiquiti/TeslaMate Pi |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 114.0 V, below the 114 V Range A limit
- independent Ting sensor 106.2 V
119. 2026-08-21 17:19:49 UNDERVOLTAGE
| Lowest reading | 104.89 V on Ubiquiti/TeslaMate Pi |
|---|---|
| Leg A / Leg B | 104.89 V / 122.97 V (18.08 V split) |
| 240 V service reference | 226.0 V |
| Meters affected | Ubiquiti/TeslaMate Pi |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 104.9 V, below the 110 V Range B limit
- independent Ting sensor 103.5 V
120. 2026-08-21 16:51:39 UNDERVOLTAGE
| Lowest reading | 107.63 V on Ubiquiti/TeslaMate Pi |
|---|---|
| Leg A / Leg B | 107.63 V / 121.16 V (13.53 V split) |
| 240 V service reference | 226.4 V |
| Meters affected | Ubiquiti/TeslaMate Pi |
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 107.6 V, below the 110 V Range B limit
- independent Ting sensor 106.8 V
121. 2026-08-21 16:29:02 UNDERVOLTAGE
| Lowest reading | 104.01 V on Ubiquiti/TeslaMate Pi |
|---|---|
| Leg A / Leg B | 104.01 V / 118.75 V (14.73 V split) |
| 240 V service reference | 222.5 V |
| Meters affected | Ubiquiti/TeslaMate Pi |
retained 2026-08-21 16:28:50 = 86.35 V (exact timestamp)
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 104.0 V, below the 110 V Range B limit
- independent Ting sensor 86.3 V
122. 2026-08-21 16:28:51 UNDERVOLTAGE
| Lowest reading | 104.52 V on Ubiquiti/TeslaMate Pi |
|---|---|
| Leg A / Leg B | 104.01 V / 118.75 V (14.73 V split) |
| 240 V service reference | 222.5 V |
| Meters affected | Ubiquiti/TeslaMate Pi |
retained 2026-08-21 16:28:50 = 86.35 V (exact timestamp)
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 104.5 V, below the 110 V Range B limit
- independent Ting sensor 86.3 V
123. 2026-08-21 10:14:44 UNDERVOLTAGE
| Lowest reading | 104.49 V on Ubiquiti/TeslaMate Pi |
|---|---|
| Leg A / Leg B | 104.49 V / 123.26 V (18.77 V split) |
| 240 V service reference | 225.9 V |
| Meters affected | Ubiquiti/TeslaMate Pi |
retained 2026-08-21 10:14:47 = 97.71 V (exact timestamp)
Ting samples faster than the branch meters, so this is the closer estimate of the real extreme.
- branch meter 104.5 V, below the 110 V Range B limit
- independent Ting sensor 97.7 V