Voltage Irregularities

Brieske residence, Orcutt CA

Mon Aug 17, 1:00 PM to Wed Sep 23, 9:40 AM

Friday, August 21, 2026

10:14:44 AMLOW97.7 V †5 s
4:28:51 PMLOW86.3 V †5 s
4:29:02 PMLOW86.3 V †18 s
4:51:39 PMLOW106.8 V †2 s
5:19:49 PMLOW103.5 V †11 s
7:50:57 PMLOW106.2 V †2 s
7:51:42 PMLOW106.0 V2 s

Saturday, August 22, 2026

9:41:20 PMLOW105.7 V †2 s
10:28:30 PMLOW106.1 V †2 s
11:01:30 PMLOW112.0 V2 s
11:02:00 PMLOW108.6 V2 s

Sunday, August 23, 2026

1:52:44 AMLOW107.0 V2 s
2:20:21 AMLOW106.1 V †11 s
7:34:13 AMLOW107.2 V †2 s
3:04:33 PMLOW106.1 V †2 s
3:24:40 PMLOW105.2 V †2 s
4:31:26 PMLOW84.8 V †17 s

Tuesday, September 1, 2026

9:14:49 PMLOW114.0 V7 s
9:15:16 PMLOW113.2 V2 min 45 s

Wednesday, September 23, 2026

12:00:22 AMLOW113.8 V3 s
20 in this window  ·  20 low (lowest 84.8 V)  ·  4 min 24 s out of range
Also recorded but not listed individually: 32 brief high readings on a 120 V branch meter, peaking at 127.4 V. These are held back for two reasons: readings between 126 V and 127 V are inside ANSI Range B, which the standard tolerates as occasional; and none of them were confirmed by the neutral-independent 240 V line-to-line reference, which never left its limits. They are reported as a count so that nothing is hidden, not because they are being claimed.
† measured by the Ting sensor, which samples faster than once per second and therefore resolves brief excursions the 1 s branch meters average away. LOW = below 114 V. Normal service is 114–126 V (ANSI C84.1 Range A) at 120 V nominal. A HIGH row appears only when the neutral-independent 240 V line-to-line reference also left its limits.