VOLTAGE IRREGULARITIES — Brieske residence, Orcutt CA Window: Mon Aug 17, 1:00 PM to Wed Sep 23, 10:17 AM ======================================================== Fri Aug 21, 2026 10:14:44 AM LOW 97.7 V † 5 s 4:28:51 PM LOW 86.3 V † 5 s 4:29:02 PM LOW 86.3 V † 18 s 4:51:39 PM LOW 106.8 V † 2 s 5:19:49 PM LOW 103.5 V † 11 s 7:50:57 PM LOW 106.2 V † 2 s 7:51:42 PM LOW 106.0 V 2 s Sat Aug 22, 2026 9:41:20 PM LOW 105.7 V † 2 s 10:28:30 PM LOW 106.1 V † 2 s 11:01:30 PM LOW 112.0 V 2 s 11:02:00 PM LOW 108.6 V 2 s Sun Aug 23, 2026 1:52:44 AM LOW 107.0 V 2 s 2:20:21 AM LOW 106.1 V † 11 s 7:34:13 AM LOW 107.2 V † 2 s 3:04:33 PM LOW 106.1 V † 2 s 3:24:40 PM LOW 105.2 V † 2 s 4:31:26 PM LOW 84.8 V † 17 s Tue Sep 1, 2026 9:14:49 PM LOW 114.0 V 7 s 9:15:16 PM LOW 113.2 V 2 min 45 s Wed Sep 23, 2026 12:00:22 AM LOW 113.8 V 3 s -------------------------------------------------------- TOTAL: 20 irregularities · 20 low (lowest 84.8 V) · 4 min 24 s out of range Also recorded but not listed individually: 32 brief high readings on a 120 V branch meter, peaking at 127.4 V. These are held back for two reasons: readings between 126 V and 127 V are inside ANSI Range B, which the standard tolerates as occasional; and none of them were confirmed by the neutral-independent 240 V line-to-line reference, which never left its limits. They are reported as a count so that nothing is hidden, not because they are being claimed. † measured by the Ting sensor, which samples faster than once per second and therefore resolves brief excursions the 1 s branch meters average away. LOW = below 114 V. Normal service is 114–126 V (ANSI C84.1 Range A) at 120 V nominal. A HIGH row appears only when the neutral-independent 240 V line-to-line reference also left its limits.