VOLTAGE IRREGULARITY REPORT — Brieske residence, Orcutt CA ==================================================================== Window: Last 30 days Mon Aug 24, 11:03 AM to Wed Sep 23, 11:03 AM Generated: 2026-09-23 11:03:31 PDT Coverage: 39,183 samples logged today across 87 retained detail files. Measurement method: three TP-Link EP25 metering outlets record true-RMS line voltage once per second on both 120 V legs of the split-phase service. A Tesla Wall Connector supplies the 240 V line-to-line reference and grid frequency, which is independent of the neutral. A Ting (Whisker) sensor on Leg A samples far faster than 1 Hz and retains the lowest and highest voltage it sees, so it resolves brief excursions that a 1 s RMS average necessarily flattens in both directions. Where the two disagree, the Ting figure is the closer estimate of the real extreme. What is listed: any reading below 114 V (the ANSI C84.1 Range A lower limit) and any reading above 127 V (the Range B upper limit) at 120 V nominal. Undervoltage dims and stalls equipment; sustained overvoltage damages it, so both are reported. Also recorded but not listed individually: 5 brief high readings on a 120 V branch meter, peaking at 126.7 V. These are held back for two reasons: readings between 126 V and 127 V are inside ANSI Range B, which the standard tolerates as occasional; and none of them were confirmed by the neutral-independent 240 V line-to-line reference, which never left its limits. They are reported as a count so that nothing is hidden, not because they are being claimed. SUMMARY -------------------------------------------------------------------- Irregularities listed: 3 (3 low, 0 high) Corroborated by Ting: 2 Lowest branch reading: 113.19 V (Ting 118.50 V) Lowest 240 V reference: 233.1 V Total time out of range: 2 min 55 s By hour of day: 00:00 x1, 21:00 x2 IRREGULARITIES (newest first) ==================================================================== [1] 2026-09-23 00:00:22 — LOW Duration: 3 seconds (4 samples out of range) Extreme: 113.75 V on 3D Printer - Mikes Room (outside Range A) Leg A: 120.55 V Leg B: 116.73 V split 3.82 V 240 V ref: 235.9 V Pattern: MINOR LEG IMBALANCE Meters: 3D Printer - Mikes Room Why listed: branch meter 113.8 V, below the 114 V Range A limit [2] 2026-09-01 21:15:16 — LOW Duration: 2 minutes 45 seconds (166 samples out of range) Extreme: 113.19 V on 3D Printer - Mikes Room (outside Range A) TING: 118.50 V <-- independent Leg A sensor Leg A: 120.36 V Leg B: 113.45 V split 6.91 V 240 V ref: 233.1 V Pattern: LOCAL/BRANCH DROP Meters: 3D Printer - Mikes Room, Computer and TV - Mikes Room Why listed: branch meter 113.2 V, below the 114 V Range A limit [3] 2026-09-01 21:14:49 — LOW Duration: 7 seconds (8 samples out of range) Extreme: 113.96 V on 3D Printer - Mikes Room (outside Range A) TING: 118.50 V <-- independent Leg A sensor Leg A: 120.36 V Leg B: 113.45 V split 6.91 V 240 V ref: 233.1 V Pattern: LOCAL/BRANCH DROP Meters: 3D Printer - Mikes Room Why listed: branch meter 114.0 V, below the 114 V Range A limit ==================================================================== Labels describe the simultaneous meter pattern. They do not assert a confirmed physical cause; that determination belongs to the utility or electrician after inspecting the service.